D - 31
Appendix D
•
Vission 20/20 Communication Table
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Vilter
TM
Address
Ethernet
IP
Address
Modbus
Address
Command Name
Data
Type
Value
Mode
Lower
Range
Higher
Range
582
N73:41
41511
Trend Files Location
ENUM
"0 = Hard Disk
1 = USB Drive"
Read
Configuration (Time)
583
N76:0
41330
Time – Hours
INT
(HH)
Read-Write 0
23
584
N76:1
41331
Time – Min
INT
(MM)
Read-Write 0
59
585
N76:2
41332
Time – Secs
INT
(SS)
Read-Write 0
59
586
N76:3
41333
Date – Year
INT
(YYYY)
Read-Write 1970
2037
587
N76:4
41334
Date – Month
INT
(1-12)
Read-Write 1
12
588
N76:5
41335
Date – Day
INT
(1-31)
Read-Write 1
31
Configuration (Other)
589
N77:0
41340
Anti-Recycle
ENUM
"0 = True Anti-Recycle
1 = Accumulative Anti-
Recycle
2 = Hot Starts"
Read
590
N77:1
41341
Restart On Power Fail
ENUM
"0 = Always
1 = Never
2 = Timed
3 = Remote Lock Off
4 = Boot in Remote
(Direct I/O)"
Read-Write
591
N77:2
41342
Suction Pressure
Control Available
INT
0 = No, 1 = Yes
Read
592
N77:3
41343
Suction Pressure
Control # of Setpoints
INT
Read
593
N77:4
41344
Process Control
Available
INT
0 = No, 1 = Yes
Read
594
N77:5
41345
Process Control # of
Setpoints
INT
Read
595
N77:6
41346
% Slide Volume
Position
INT
0 = No, 1 = Yes
Read
596
N77:7
41347
Economizer Pressure
INT
0 = No, 1 = Yes
Read
597
N77:8
41348
Compressor VFD
INT
0 = No, 1 = Yes
Read
598
N77:9
41349
Compressor
Sequencing
INT
0 = No, 1 = Yes
Read
599
N77:10
41350
Superheat Monitor
INT
0 = No, 1 = Yes
Read
600
N77:11
41351
Oil Pump Control
Type
ENUM
"0 = No Pump
1 = Stal
2 = Cycling
3 = Full Time
4 = Cool Compression
5 = Suction Oil Injection
Solenoid"
Read
Summary of Contents for Vilter Vission 20/20
Page 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Page 2: ......
Page 4: ......
Page 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Page 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Page 336: ......
Page 337: ......