![EDM Solution 862 Installation Manual Download Page 42](http://html1.mh-extra.com/html/edm/solution-862/solution-862_installation-manual_2362278042.webp)
42
Solution 862
Installation Manual
Defaulting The Control Panel
If the
Solution 862
control panel does not have "LOCATION 900" programmed as 15,
follow the procedure outlined below to successfully default the control panel back to the
factory default settings.
How To Default The Control Panel Via Installer Code
1.
Enter Installer Programming Mode.
(e.g..
1234
followed by the
#
button). Two beeps will be heard. The
STAY
and
AWAY
indicators will begin to flash to indicate that you have accessed
programming mode.
2.
Enter Installer’s Programming Command
965
followed by the
#
button.
Two beeps will be heard after the control panel has successfully been defaulted.
3.
Enter Installer’s Programming Command 960 followed by the # button.
Two beeps will be heard. The
STAY
and
AWAY
indicators will cease to flash and the
system will return to the disarmed state.
The control panel has now been successfully defaulted back to the factory default
settings.
How To Default The Control Panel Via Default Button
1.
Disconnect the AC mains supply and the backup battery from the control panel.
2.
Hold down and continue to hold down the DEFAULT button.
The default button is located at the top of the PCB next to the PROGRAMMING KEY
connecting socket.
3.
Reconnect the AC mains supply to the control panel.
4.
After reconnecting the AC mains supply, wait for 3-5 seconds before releasing the
DEFAULT button.
5.
Disarm the system using the default Master Code (e.g.. Enter
2580
followed by
the
#
button).
The control panel has now been successfully defaulted back to the factory default
settings.
If you hear the dialler seize relay (RL2) click four times while attempting to default the
control panel, this would indicate that the feature of defaulting the control panel has
been disabled in “LOCATION 900” on page 41. The control panel will need to be returned
to Electronics Design and Manufacturing Pty Limited for exchange where a service fee
will be charged to unlock the control panel's memory if the Installer Code is not known.
ISSUE130
Electronics Design and Manufacturing Pty Limited
Summary of Contents for Solution 862
Page 1: ...Solution 862 Installation Manual ISSUE 1 30...
Page 2: ......
Page 4: ......
Page 6: ......
Page 74: ...74 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 118: ...118 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 149: ...User Codes This section includes the following Installer Code User Codes User Code Priority...
Page 154: ...154 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 188: ...188 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 212: ...212 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 228: ...228 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 240: ...240 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 245: ...Programming Sheets...
Page 254: ...254 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 255: ...Index...
Page 262: ......