System and Consumer Options
219
Consumer Options 1
LOCATION 428
0
Option
Description
1
Test Reports Only When Armed
2
Test Report After Siren Reset
4
Auto Arm In STAY Mode 1
8
STAY Indicator To Display Day Alarm Status
1
2
4
8
Table 129: Consumer Options 1
Test Reports Only When Armed
If this option has been selected, test reports (Contact ID Event Code 602) will only be sent
when the system has been armed in AWAY Mode, STAY Mode 1 or STAY Mode 2. It is no
longer necessary to send a test report as well as an opening and closing report every day.
During the working week, most commercial premises would be open and therefore a test report
is not necessary, as open and close reports would be sent at the time programmed. If you wish
to manually send a test report, hold down the
9
button until two beeps are heard.
Refer to Test Reporting Time on page 187 to set the test report time required. To set the first
test report, refer to the Installer Code Function - Set The Number Of Days Until The First Test
Report on page 77.
Test Report After Siren Reset
Selecting this option will force the control panel to send a test report after the siren has reset.
This can be used to indicate to the monitoring station that the control panel itself has not been
tampered with during the alarm period.
Auto Arm In STAY Mode 1
If automatic arming in STAY Mode 1 is preferred to automatic arming in AWAY Mode, this
option will need to be selected.
Refer to “LOCATION 414 - 417” on page 208 to program the time that the control panel will
automatically arm itself and “LOCATION 413” on page 208 to set the auto arming pre-alert
time.
STAY Indicator To Display Day Alarm Status
If this option has been selected, the
STAY
indicator will be used to display when day alarm has
been enabled. The
STAY
indicator will flash once every 3 seconds while day alarm is active.
Refer to “LOCATION 265” on page 156 for programming zones to operate for day alarm
operation.
Day alarm can be turned on and off by holding down the
4
button for 2 seconds. Three beeps
indicate day alarm is turned on and two beeps indicate day alarm is turned off. Refer to Day
Alarm Operation on page 157 for more information.
Electronics Design and Manufacturing Pty Limited
ISSUE130
Summary of Contents for Solution 862
Page 1: ...Solution 862 Installation Manual ISSUE 1 30...
Page 2: ......
Page 4: ......
Page 6: ......
Page 74: ...74 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 118: ...118 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 149: ...User Codes This section includes the following Installer Code User Codes User Code Priority...
Page 154: ...154 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 188: ...188 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 212: ...212 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 228: ...228 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 240: ...240 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 245: ...Programming Sheets...
Page 254: ...254 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 255: ...Index...
Page 262: ......