196
Solution 862
Installation Manual
23
Alarm When In AWAY Mode
This output will operate whenever an audible or silent zone alarm has triggered
when the system has been armed in AWAY Mode. The output will reset when the
system has been disarmed.
24
Mimic System Fault
This output will operate without any time delays as soon as any system fault occurs
including if the AC mains supply has failed. The output will reset as soon as the
system fault or the AC mains supply has restored.
25
Fire Alarm Resetting
This output will operate when a 24 hour fire zone is triggered. The output will reset
once a valid user code has been entered or when siren run time expires.
26
Fire Alarm Latching
This output will operate when a 24 hour fire zone has triggered and will reset when
the system has been armed or disarmed.
27
Fire Alarm Verification
This feature is used on some commercial fire control panels to reduce false alarms
on smoke detectors. It is conceptually very similar to zone pulse count as used in
some motion detectors. Basically, a fire zone is allotted a pulse count of 3 pulses
over a period of 3 minutes.
If the smoke detector trips, the voltage to the smoke detector is disconnected for 15
seconds and then reapplied. No alarm has registered.
If within 3 minutes of the first trigger the unit triggers again, no alarm will be
registered and the voltage to the smoke detector will again be disconnected for 15
seconds and then reapplied.
If a third trigger is detected within 3 minutes of the first trigger, (i.e. 3 pulses in 3
minutes) a fire alarm will be registered. Power to the smoke detector will be
maintained to facilitate unit identification via the detector memory.
This output should be connected to the negative side of any fire/smoke detector. To
configure an output for this feature, use the following settings.
EVENT TYPE = 2,7
POLARITY = 10
TIMEBASE = 2
MULTIPLIER = 15
The zone that the fire/smoke detector is connected to should be programmed as
follows:
ZONE TYPE = 13
ZONE PULSE COUNT = 3
ZONE PULSE COUNT TIME = 15
ISSUE130
Electronics Design and Manufacturing Pty Limited
Summary of Contents for Solution 862
Page 1: ...Solution 862 Installation Manual ISSUE 1 30...
Page 2: ......
Page 4: ......
Page 6: ......
Page 74: ...74 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 118: ...118 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 149: ...User Codes This section includes the following Installer Code User Codes User Code Priority...
Page 154: ...154 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 188: ...188 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 212: ...212 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 228: ...228 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 240: ...240 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 245: ...Programming Sheets...
Page 254: ...254 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Page 255: ...Index...
Page 262: ......