EDR-5000
IM02602007E
Setting Group Parameters of the Q->&V< Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Q->&V<
/General Settings]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Q->&V<
/General Settings]
LOP Blo
Activates the use of the measuring circuit supervision. In
this case the module will be blocked if a measuring circuit
supervision module (e.g. LOP, VTS) signals a disturbed
measuring circuit (e.g. caused by a fuse failure).
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Q->&V<
/General Settings]
V Ext Release PCC
Fc
Activate the release signal of the Point of Common
Coupling. The line-to-line voltage is greater than 95% of
VN.
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Q->&V<
/General Settings]
QV-Method
Selection of the Q(V)-Method: Power Angle or Reactive
Power Threshold
Power Angle Super-
vision,
Pure Reactive
Power Superv
Power Angle
Supervision
[Protection Para
/<1..4>
/Q->&V<
/Decoupling]
I1 Release
Activation of the "I1 Minimum Current"-Criterion.
Only available if: QV-Method = Power Angle Supervision
Inactive,
Active
Active
[Protection Para
/<1..4>
/Q->&V<
/Decoupling]
I1 min QV
Activation of an I1 Minimum Current of the rated current
of the (distributed) energy resource can prevent faulty
tripping.
Only available if:Activation of the "I1 Minimum Current"-
Criterion. = Active
0.01 - 0.20In
0.10In
[Protection Para
/<1..4>
/Q->&V<
/Decoupling]
VLL< QV
Undervoltage threshold (line-to-line voltage!)
0.70 - 1.00Vn
0.85Vn
[Protection Para
/<1..4>
/Q->&V<
/Decoupling]
www.eaton.com
738