EDR-5000
IM02602007E
Parameter
Description
Setting range
Default
Menu path
Trigger47
Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds
-.-
[Control
/Bkr
/Trip Manager]
Trigger48
Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds
-.-
[Control
/Bkr
/Trip Manager]
Trigger49
Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds
-.-
[Control
/Bkr
/Trip Manager]
Trigger50
Open Command to the Breaker if the state of the
assigned signal becomes true.
1..n, Trip Cmds
-.-
[Control
/Bkr
/Trip Manager]
Synchronism
Synchronism
1..n, In-SyncList
-.-
[Control
/Bkr
/Synchron Switchg]
t-MaxSyncSuperv
Synchron-Run timer: Max. time allowed for synchronizing
process after a close initiate. Only used for
GENERATOR2SYSTEM working mode.
0 - 3000.00s
0.2s
[Control
/Bkr
/Synchron Switchg]
t-Move CLOSE
Time to move to the CLOSE Position
0.01 - 100.00s
0.1s
[Control
/Bkr
/General Settings]
t-Move OPEN
Time to move to the OPEN Position
0.01 - 100.00s
0.1s
[Control
/Bkr
/General Settings]
www.eaton.com
408