EDR-5000
IM02602007E
Interlockings
There are three interlocking inputs for each switching direction (OPEN/CLOSE) available. Switching into the
corresponding switching direction can be inhibited via these inputs. Please note: The Protection Trip commands and the
reclosure command of the auto reclosure module will be issued without interlocking. In cases when the breaker must
not be opened, the protection trip command has to be inhibited by a separate blocking signal.
www.eaton.com
399