EDR-5000
IM02602007E
General Settings
In the menu [Control/Breaker/General Settings], the moving times for opening and closing of the breaker can be set.
Trip Manager
In the Trip Manger all tripping commands are combined by an “OR” logic. The actual tripping command to the breaker
is exclusively given by the Trip Manager. This means, that only tripping commands which are assigned in the Trip
Manager lead to an operation of the breaker. In addition to that, the User can set the minimum hold time of the tripping
command within this module and define whether the tripping command is latched or not.
Tripable Elements:
Name
Description
-.-
No assignment
50P[1].TripCmd
Signal: Trip Command
50P[2].TripCmd
Signal: Trip Command
50P[3].TripCmd
Signal: Trip Command
51P[1].TripCmd
Signal: Trip Command
51P[2].TripCmd
Signal: Trip Command
51P[3].TripCmd
Signal: Trip Command
50X[1].TripCmd
Signal: Trip Command
50X[2].TripCmd
Signal: Trip Command
51X[1].TripCmd
Signal: Trip Command
51X[2].TripCmd
Signal: Trip Command
50R[1].TripCmd
Signal: Trip Command
50R[2].TripCmd
Signal: Trip Command
51R[1].TripCmd
Signal: Trip Command
51R[2].TripCmd
Signal: Trip Command
27M[1].TripCmd
Signal: Trip Command
27M[2].TripCmd
Signal: Trip Command
59M[1].TripCmd
Signal: Trip Command
59M[2].TripCmd
Signal: Trip Command
27A[1].TripCmd
Signal: Trip Command
27A[2].TripCmd
Signal: Trip Command
59A[1].TripCmd
Signal: Trip Command
59A[2].TripCmd
Signal: Trip Command
59N[1].TripCmd
Signal: Trip Command
59N[2].TripCmd
Signal: Trip Command
LVRT.TripCmd
Signal: Trip Command
www.eaton.com
395