EDR-5000
IM02602007E
Direct Commands of the System Module
Parameter
Description
Setting range
Default
Menu path
Ack RO LED Comm
TCmd
Reset the Relay Outputs, LEDs, Communication, and the
Trip Command.
Inactive,
Active
Inactive
[Operation
/Reset]
Ack LED
All acknowledgeable LEDs will be acknowledged.
Inactive,
Active
Inactive
[Operation
/Reset]
Ack RO
All acknowledgeable Relay Outputs will be
acknowledged.
Inactive,
Active
Inactive
[Operation
/Reset]
Ack Comm
Communication will be acknowledged.
Inactive,
Active
Inactive
[Operation
/Reset]
Reboot
Rebooting the device.
No,
Yes
No
[Service
/General]
MaintMode
Manually
Arc Flash Reduction Maintenance Switch Mode: Manual
Activation of the Arc Flash Reduction Mode
Only available if: Maint Mode = Activation Manually
Maint Mode inacti-
ve,
Activation via
Comm,
Activation via DI,
Inactive,
Active
Inactive
[Service
/MaintMode
Manually]
Program Mode
Bypass
Short-period bypass of the Program Mode.
Inactive,
Active
Inactive
[System Para
/General Settings]
CAUTION: Manually rebooting the device will release the Supervision Contact.
www.eaton.com
287