EDR-5000
IM02602007E
Selection List for Logic Input Signals
Name
Description
-.-
No assignment
Prot.Active
Signal: Active
Prot.Available
Signal: Protection is available.
Prot.I dir fwd
Signal: Phase current failure forward direction
Prot.I dir n poss
Signal: Phase fault - missing reference voltage
Prot.I dir rev
Signal: Phase current failure reverse direction
Prot.IR dir fwd
Signal: IR Ground fault (calculated) forward
Prot.IR dir n poss
Signal: IR Ground fault (calculated) direction detection not possible
Prot.IR dir rev
Signal: IR Ground fault (calculated) reverse direction
Prot.IX dir fwd
Signal: IX Ground fault (measured) forward
Prot.IX dir n poss
Signal: IX Ground fault (measured) direction detection not possible
Prot.IX dir rev
Signal: IX Ground fault (measured) reverse direction
Prot.Pickup
Signal: General Pickup
Prot.Trip
Signal: General Trip
Bkr.SI SingleContactInd
Signal: The Position of the Switchgear is detected by one auxiliary contact (pole) only. Thus indeterminate
and disturbed Positions cannot be detected.
Bkr.Pos not CLOSE
Signal: Pos not CLOSE
Bkr.Pos CLOSE
Signal: Breaker is in CLOSE-Position
Bkr.Pos OPEN
Signal: Breaker is in OPEN-Position
Bkr.Pos Indeterm
Signal: Breaker is in Indeterminate Position
Bkr.Pos Disturb
Signal: Breaker Disturbed - Undefined Breaker Position. The feed-back signals (Position Indicators) contradict
themselves. After expiring of a supervision timer this signal becomes true.
Bkr.Ready
Signal: Breaker is ready for operation.
Bkr.Interl CLOSE
Signal: One or more IL_Close inputs are active.
Bkr.Interl OPEN
Signal: One or more IL_Open inputs are active.
Bkr.CES succesf
Signal: Command Execution Supervision: Switching command executed successfully.
Bkr.CES Disturbed
Signal: Command Execution Supervision: Switching Command unsuccessful. Switchgear in disturbed
position.
Bkr.CES Fail TripCmd
Signal: Command Execution Supervision: Command execution failed because trip command is pending.
Bkr.CES SwitchgDir
Signal: Command Execution Supervision respectivly Switching Direction Control: This signal becomes true, if
a switch command is issued even though the switchgear is already in the requested position. Example: A
switchgear that is already OPEN should be switched OPEN again (doubly). The same applies to CLOSE
commands.
Bkr.CES CLOSE d OPEN
Signal: Command Execution Supervision: CLOSE Command during a pending OPEN Command.
Bkr.CES SG not ready
Signal: Command Execution Supervision: Switchgear not ready
Bkr.CES Field Interl
Signal: Command Execution Supervision: Switching Command not executed because of field interlocking.
Bkr.CES SyncTimeout
Signal: Command Execution Supervision: Switching Command not executed. No Synchronization signal while
t-sync was running.