
EDR-5000
IM02602007E
Setting Group Parameters of the Module Automatic Reclosure
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/AR
/General Settings]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/AR
/General Settings]
Zone coordination
Zone coordination: Sequence coordination is to keep
upstream reclosers in step with the downstream ones for
fast and delay curve operation, thus avoiding
overtripping.
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/AR
/General Settings]
Ex Shot Inc Fc
The AR Shot counter will be incremented by this external
Signal. This can be used for Zone Coordination (of
upstream Auto Reclosure devices). Note: This parameter
enables the functionallity only. The assignment has to be
set within the global parameters.
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/AR
/General Settings]
Ex Lock Fc
The auto reclosure will locked out by this external Signal.
Note: This parameter enables the functionallity only. The
assignment has to be set within the global parameters.
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/AR
/General Settings]
Reset Mode
Reset Mode
auto,
HMI,
DI,
Comm,
HMI And Comm,
HMI And DI,
Comm And DI,
HMI And DI
auto
[Protection Para
/<1..4>
/AR
/General Settings]
Shots
Maximum number of permitted reclosure attempts.
1 - 6
1
[Protection Para
/<1..4>
/AR
/General Settings]
www.eaton.com
578