EDR-5000
IM02602007E
Device Planning Parameters of the Sync-check Module
Parameter
Description
Options
Default
Menu path
Mode
Mode
Do not use,
Use
Use
[Device Planning]
Global Protection Parameter of the Sync-check Module
Parameter
Description
Setting range
Default
Menu path
ExBlo1
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Sync]
ExBlo2
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Sync]
Bypass
The Sync-check will be bypassed if the state of the
assigned signal (logic input) becomes true.
1..n, DI-LogicList
-.-
[Protection Para
/Global Prot Para
/Sync]
BkrCloseInitiate
Breaker Close Initiate with synchronism check from any
control sources (e.g. HMI / SCADA). If the state of the
assigned signal becomes true, a Breaker Close will be
initiated (Trigger Source).
1..n,
SyncRequestList
-.-
[Protection Para
/Global Prot Para
/Sync]
www.eaton.com
638