
EDR-5000
IM02602007E
Setting Group Parameters of the BF
In order to prevent a faulty activation of the BF Module, the pickup (alarm) time
must be greater than the sum of:
Operating time of the protective relay
+The close-open time of the breaker (please refer to the technical data of
the manufacturer of the breaker);
+Drop off time (current- or position indicators)
+Security margin.
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Supervision
/BF]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Supervision
/BF]
I-BF >
Current level that needs to exist after Trip Command has
been given.
Only available if: Scheme50BF = Or Scheme = 50BF and
CB Pos
0.02 - 4.00In
0.02In
[Protection Para
/<1..4>
/Supervision
/BF]
t-BF
If the delay time is expired, an BF alarm is given out.
0.00 - 10.00s
0.20s
[Protection Para
/<1..4>
/Supervision
/BF]
www.eaton.com
775