EDR-5000
IM02602007E
Device Planning Parameters of the Low-Voltage-Ride-Through
Parameter
Description
Options
Default
Menu path
Mode
Mode
Do not use,
Use
Do not use
[Device Planning]
Setting Group Parameters of the Low-Voltage-Ride-Through
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/LVRT
/General Settings]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/LVRT
/General Settings]
Blo TripCmd
Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/LVRT
/General Settings]
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/LVRT
/General Settings]
Measuring Mode
Measuring/Supervision Mode: Determines if the phase-
to-phase or phase-to-earth voltages are to be
supervisioned
Phase to Ground,
Phase to Phase
Phase to Ground [Protection Para
/<1..4>
/LVRT
/General Settings]
www.eaton.com
750