EDR-5000
IM02602007E
Setting Group Parameters of the LOP Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Supervision
/LOP]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Supervision
/LOP]
LOP Blo Enable
Activate (allow) or inactivate (disallow) blocking by the
module LOP.
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Supervision
/LOP]
t-Pickup
Pickup Delay
0 - 9999.0s
0.1s
[Protection Para
/<1..4>
/Supervision
/LOP]