2 Functions of Devices in DVP-PLC
DVP-PLC Application Manual
2-3
N
For Master control loop
N0 ~ N7, 8 points
Control point for main
control loop
P
For CJ, CALL instructions
P0 ~ P255, 256 points
Position index for CJ
and CALL
External interruption
I001, I101, I201, I301, I401, I501, total 6 points
Timed interruption
I6
□□
, I7
□□
, 2 points (
□□
= 1 ~ 99, time
base = 1ms)
Interruption inserted when
high-speed counter
reaches target
I010, I020, I030, I040, I050, I060, total 6 points
Pointer
I
Interruption
Communication interruption I150, 1 point
Position index for
interruption subroutine.
K Decimal
form
K-32,768 ~ K32,767 (16-bit operation)
K-2,147,483,648 ~ K2,147,483,647 (32-bit operation)
Const
a
nt
H Hexadecimal
form
H0000 ~ HFFFF (16-bit operation)
H00000000 ~ HFFFFFFFF (32-bit operation)
*1. Non-latched area cannot be modified.
*2. The preset non-latched area can be modified into latched area by setting up parameters.
*3. The preset latched area can be modified into non-latched area by setting up parameters.
*4. The fixed latched area cannot be modified
Latched settings for all devices in SA/SX/SC series MPU:
General purpose
Latched
Special auxiliary relay
Latched
M0 ~ M511
M512 ~ M999
M1000 ~ M1999
M2000 ~ M4095
Default: latched
Default: latched
M
(Auxiliary relay)
It is fixed to be non-latched
Start: D1200 (K512)
End: D1201 (K999)
Some are latched and
cannot be modified
Start: D1202 (K2,000)
End: D1203 (K4,095)
100 ms
10 ms
10 ms
1 ms
100 ms
T0 ~ T199
T200 ~ T239
T240 ~ T245
T246 ~ T249
T250 ~ T255
T
(Timer)
It is fixed to be non-latched It is fixed to be non-latched
Accumulative type
It is fixed to be latched
16-bit counting up
32-bit counting up/down
32-bit high-speed counting
up/down
C0 ~ C95
C96 ~ C199
C200 ~ C215
C216 ~ C234
C235 ~ C255
Default: latched
Default: latched Default:
latched
C
(Counter)
It is fixed to be
non-latched
Start: D1208 (K96)
End: D1209 (K199)
It is fixed to be
non-latched
Start: D1210 (K216)
End: D1211 (K234)
Start: D1212 (K235)
End: D1213 (K255)
Initial
Zero return
General purpose
Latched
Alarm step
S0 ~ S9
S10 ~ S19
S20 ~ S511
S512 ~ S895
S896 ~ S1023
Default: latched
S
(Step relay)
It is fixed to be non-latched
Start: D1214 (K512)
End: D1215 (K895)
It is fixed to be latched
General purpose
Latched
Special register
Latched
D0 ~ D199
D200 ~ D999
D1000 ~ D1999
D2000 ~ D4999
Default: latched
Default: latched
D
(Register)
It is fixed to be non-latched
Start: D1216 (K200)
End: D1217 (K999)
Some are latched and
cannot be modified.
Start: D1218 (K2,000)
End: D1219 (K4,999)
K0 ~ K1599
File Register
It is fixed to be latched.
Summary of Contents for DVP-PLC
Page 1: ...PLC PLC...
Page 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Page 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Page 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Page 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...