7 Application Instructions API 50-99
D V P - P L C A P P L I C AT I O N M A N U A L
7-47
Lower bound value
Upper bound value
Present value in C10
Output
D104 = 140
D105 = 170
140
≦
C10
≦
170
M12 = On
D106 = 150
D107 = 390
150
≦
C10
≦
390
M13 = On
5. If the lower bound value > upper bound value, when C10 < upper bound value (60) or > upper bound value (140),
M12 will be On.
Lower bound value Upper bound value
Present value in C10
Output
D100 = 40
D101 = 100
40
≦
C10
≦
100
M10 = On
D102 = 120
D103 = 210
120
≦
C10
≦
210
M11 = On
D104 = 140
D105 = 60
60
≦
C10
≦
140
M12 = On
D106 = 150
D107 = 390
150
≦
C10
≦
390
M13 = On
400
200
0
40
100
120
210
60
140
150
390
M10
M11
M12
M13