6 Application Instructions API 00-49
DVP-PLC Application Manual
6-39
API Mnemonic
Operands
Function
24
D INC P
Increment
Controllers
ES/EX/SS SA/SX/SC EH/SV
Bit Devices
Word Devices
Program Steps
Type
OP
X Y M S K H
KnX
KnY KnM KnS T C D E F
D
*
*
*
*
*
*
*
*
INC, INCP: 3 steps
DINC, DINCP: 5 steps
PULSE 16-bit 32-bit
ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV
Operands:
D
: Destination device
Explanations:
1. If
D
is used in device F, only 16-bit instruction is applicable.
2.
See the specifications of each model for their range of use.
3.
If the instruction is not a pulse execution one, the content in the designated device D will plus “1” in every scan
period whenever the instruction is executed.
4.
This instruction adopts pulse execution instructions (INCP, DINCP).
5.
In 16-bit operation, 32,767 pluses 1 and obtains -32,768. In 32-bit operation, 2,147,483,647 pluses 1 and
obtains -2,147,483,648.
6.
The operation results will not affect M1020 ~ M1022.
Program Example:
When X0 = Off
→
On, the content in D0 pluses 1 automatically.
X0
INCP
D0