2 Functions of Devices in DVP-PLC
DVP-PLC Application Manual
2-82
3.
Particularly for HKY instruction, when the 16-digit button input is operated by 4x4 matrix, the scan time has to be
fixed to longer than 20ms.
4.
The scan time in D1010 ~ D1012 also includes fixed scan time.
Function Group
Analog Function
Number
D1056 ~ D1059, D1062, D1110 ~ D1113, D1116 ~ D1118
Contents:
1.
Resolution of analog input channel: 10 bits for EX, corresponding to 0 ~ ±10 V (-512 ~ +511) or 0 ~ ±20 mA
(-512 ~ +511); 12 bits for SX, corresponding to 0 ~ ±10 V (-2,000 ~ +2,000) or 0 ~ ± 20 mA (-1,000 ~ +1,000).
2.
Resolution of analog output channel: 8 bits for EX, corresponding to 0 ~ 10 V (0 ~ 255) or 0 ~ 20 mA (0 ~ 255);
12 bits for SX, corresponding to 0 ~ ±10 V (-2,000 ~ +2,000) or 0 ~ ±20 mA (-2,000 ~ +2,000).
3.
Sampling time of analog/digital conversion. Default setting = 5; unit: ms. If D1118
≤
5, it will be regarded as 5ms.
4.
Resolution of EH/EH2 analog input AD card (DVP-F2AD): 12 bits 0 ~ 10 V (0 ~ +4,000) or 11 bits 0 ~ 20 mA
(0~+2,000)
5.
Resolution of EH/EH2 analog input DA card (DVP-F2DA): 12 bits 0 ~ 10 V (0 ~ +4,000) or 0 ~ 20 mA (0 ~
+4,000)
Device No.
Function
D1056
Present value of EX/SX analog input channel CH0 and EH/EH2 AD card channel CH0
D1057
Present value of EX/SX analog input channel CH1 and EH/EH2 AD card channel CH1
D1058
Present value of EX analog input channel CH 2
D1059
Present value of EX analog input channel CH 3
D1062
Average times (2 ~ 4) of SX AD0 and AD1
D1110
Average value of EX/SX analog input channel CH0 and EH/EH2 AD card channel CH0
D1111
Average value of EX/SX analog input channel CH1 and EH/EH2 AD card channel CH1
D1112
Average value of EX analog input channel CH2
D1113
Average value of EX analog input channel CH3
D1116
EX/SX analog output channel CH0 and EH/EH2 DA card channel CH0
D1117
EX/SX analog output channel CH1 and EH/EH2 DA card channel CH1
D1118
Sampling time (ms) of EX/SX/EH/EH2 analog/digital conversion
Function Group
Operational Error Flag
Number
M1067 ~ M1068, D1067 ~ D1068
Contents:
1.
Operational error flag:
Device
Description
Latched
STOP
→
RUN
RUN
→
STOP
M1067
Operational error flag
None
Cleared
Latched
M1068
Operational error locked flag
None
Latched
Latched
Summary of Contents for DVP-PLC
Page 1: ...PLC PLC...
Page 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Page 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Page 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Page 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...