2 Functions of Devices in DVP-PLC
DVP-PLC Application Manual
2-13
SA/SX/SC series MPU:
100ms general purpose
T0 ~ T199, 200 points. T192 ~ T199 are the timers for subroutine. Fixed to
be non-latched
100ms accumulative
T250 ~ T255, 6 points. Fixed to be latched.
10ms general purpose T200 ~ T239, 40 points. Fixed to be non-latched
10ms accumulative
T240 ~ T245, 6 points. Fixed to be latched.
Time T
1ms accumulative
T246 ~ T249, 4 points. Fixed to be latched.
Total
256 points
EH/EH2/SV series MPU:
100ms general purpose
T0 ~ T199, 200 points. Can be latched by setting up parameters.
T192 ~ T199 are the timers for subroutine.
100ms accumulative
T250 ~ T255, 6 points. Fixed to be latched.
10ms general purpose T200 ~ T239, 40 points. Can be latched by setting up parameters.
10ms accumulative
T240 ~ T245, 6 points. Fixed to be latched.
Timer T
1ms accumulative
T246 ~ T249, 4 points. Fixed to be latched.
Total
256 points
Functions of timers:
The units of the timer are 1ms, 10ms and 100ms and the counting method is counting up. When the present
value in the timer equals the set value, the output coil will be On. The set value should be a K value in decimal and the
data register D can also be a set value.
The actual set time in the timer = timing unit × set value
There are three types of timers:
1.
General purpose timer:
For ES/SA series MPU: The timer executes once when the program reaches END instruction. When TMR
instruction is executed, the output coil will be On when the timing reaches its target.
For EH/EH2/SV series MPU: The timer executes once when the program reaches TMR instruction. When TMR
instruction is executed, the output coil will be On when the timing reaches its target.
T0
Y0
X0
TMR
T0
K100
X0
Y0
T0
10 secs
PV
SV K100
When X0 = On, The PV in timer T0 will count up by
100ms. When the PV = SV K100, the output coil T0
will be On.
When X0 = Off or the power is off, the PV in timer T0
will be cleared as 0, and the output coil T0 will be
Off.
2.
Accumulative type timer:
For ES/SA series MPU: The timer executes once when the program reaches END instruction. When TMR
instruction is executed, the output coil will be On when the timing reaches its target.
For EH/EH2/SV series MPU: The timer executes once when the program reaches TMR instruction. When TMR
instruction is executed, the output coil will be On when the timing reaches its target.
Summary of Contents for DVP-PLC
Page 1: ...PLC PLC...
Page 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Page 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Page 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Page 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...