9 Application Instructions API 150-199
DVP-PLC Application Manual
9-92
3. Monitor the segment No. that is currently being executed in register D301.
D0
D300
END
X0
4. The pulse output curve:
Frequency (Hz)
t
t
t
t
1
2
....
60
(D1,D0)
(D3,D2)
(D239,D238)
(D5,D4)
(D237,D236)
....
....
(D7,D6)
Time (S)
Remarks:
1. Flag
explanations:
M1029
:
On when CH0 (Y0) pulse output is completed.
M1030
:
On when CH1 (Y2) pulse output is completed.
M1036
:
On when CH2 (Y4) pulse output is completed.
M1037
:
On when CH3 (Y6) pulse output is completed.
M1334
:
When On, CH0 (Y0) pulse output will be forbidden.
M1335
:
When On, CH1 (Y2) pulse output will be forbidden.
M1520
:
When On, CH2 (Y4) pulse output will be forbidden.
M1521
:
When On, CH3 (Y6) pulse output will be forbidden.
M1336
:
CH0 (Y0) pulse output indication flag
M1337
:
CH1 (Y2) pulse output indication flag
M1522
:
CH2 (Y4) pulse output indication flag
M1523
:
CH3 (Y6) pulse output indication flag
2. Special
register
explanations:
D1336, D1337
:
Pulse present value register of CH0 (Y0) (D1337 high word, D1336 low word)
D1338, D1339
:
Pulse present value register of CH1 (Y2) (D1339 high word, D1338 low word)
D1375, D1376
:
Pulse present value register of CH2 (Y4) (D1376 high word, D1375 low word)
D1377, D1378
:
Pulse present value register of CH3 (Y6) (D1378 high word, D1377 low word)
Summary of Contents for DVP-PLC
Page 1: ...PLC PLC...
Page 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Page 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Page 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Page 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...