9 Application Instructions API 150-199
DVP-PLC Application Manual
9-30
API Mnemonic
Operands
Function
159
D DRVA
Drive to Absolute
Controllers
ES/EX/SS SA/SX/SC EH/SV
Bit Devices
Word Devices
Program Steps
Type
OP
X Y M S K H
KnX
KnY KnM KnS T
C
D
E
F
S
1
*
*
*
*
*
*
*
*
*
*
*
S
2
*
*
*
*
*
*
*
*
*
*
*
D
1
*
D
2
*
*
*
DRVA: 9 steps
DDRVA: 17 steps
PULSE 16-bit 32-bit
ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV
Operands:
S
1
: Number of output pulses (absolute designation)
S
2
: Pulse output frequency
D
1
: Pulse output device
(please use transistor output module)
D
2
: Output device for the signal of rotation direction
Explanations:
1.
See remarks for the setting range of
S
1
,
S
2
,
D
1
and
D
2
.
2.
S
1
and
S
2
of SC series MPU only support device K, H and D.
3.
Flag: see remarks of API 158 DRVI for more details.
4.
S
1
is the number of output pulses (absolute designation). For EH/EH2/SV series MPU, the 16-bit instruction
can designate the range -32,768 ~ +32,767. The range designated by 32-bit instruction is -2,147,483,648 ~
+2,147,483,647. For SC series MPU, the 32-bit instruction can designate the range -2,147,483,648 ~
+2,147,483,647. “+/-” signs indicate forward/backward directions.
5.
S
2
is the designated pulse output frequency. For EH/EH2/SV series MPU, the 16-bit instruction can designate
its range 10 ~ 32,767Hz. The range designated by 32-bit instruction is 10 ~ 200,000Hz. For SC series MPU,
the 32-bit instruction can designate the range 100 ~ 100,000Hz.
6.
EH series MPU has two groups of A/B phase pulse output, CH0 (Y0, Y1) and CH1 (Y2, Y3). EH2/SV series
MPU has four groups of A/B phase pulse output, CH0 (Y0, Y1), CH1 (Y2, Y3), CH2 (Y4, Y5) and CH3 (Y6, Y7).
See remarks for the setup methods.
7.
Pulse output device
D
1
in different models
Model
SC MPU
EH MPU
EH2/SV MPU
Pulse output end
Y10, Y11
Y0, Y2
Y0, Y2, Y4, Y6
8. When
S
1
is larger than the current relative position,
D
2
will be Off; when
S
1
is smaller than the current relative
position,
D
2
will be On.
D
2
will not be Off immediately after the pulse output is over; it will be Off only when the
drive contact of the instruction turns Off.
9.
For EH/EH2/SV series MPU,
S
1
is
- The 32-bit data stored in the present value registers D1337 (high word) and D1336 (low word) of CH0 (Y0,
Y1).
- The 32-bit data stored in the present value registers D1339 (high word) and D1338 (low word) of CH1 (Y2,
Y3).
- The 32-bit data stored in the present value registers D1376 (high word) and D1375 (low word) of CH2 (Y4,
Y5).
- The 32-bit data stored in the present value registers D1378 (high word) and D1377 (low word) of CH3 (Y5,
Summary of Contents for DVP-PLC
Page 1: ...PLC PLC...
Page 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Page 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Page 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Page 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...