7 Application Instructions API 50-99
D V P - P L C A P P L I C AT I O N M A N U A L
7-78
CR#24.
FROM/TO Application Example 2:
Adjust the A/D conversion curve of DVP-04AD. Set the OFFSET value of CH2 as 2mA (= K400
LSB
) and GAIN value
as 18mA (= K3,600
LSB
).
M1002
TO
K0
K1
H18
K1
TO
K0
K33
H0
K1
X0
TO
K0
K19
K400
K1
TO
K0
K25
K3600
K1
1. Write H18 to CR#1 of anlog input module No. 0 and set CH2 as mode 3 (current input: -20mA ~ +20mA).
2. Write H0 to CR#33 and allow OFFSET/GAIN tuning in CH1 ~ CH4.
3. When X0 goes from Off to On, write the OFFSET value K400
LSB
into CR#19 and the GAIN value K3,600
LSB
into
CR#25.
FROM/TO Application Example 3:
Adjust the D/A conversion curve of DVP-02DA. Set the OFFSET value of CH2 as 0mA (= K0
LSB
) and GAIN value as
10mA (= K1,000
LSB
).
M1002
TO
K1
K1
H18
K1
TO
K1
K33
H0
K1
X0
TO
K1
K22
K0
K1
TO
K1
K28
K1000
K1
1. Write H18 to CR#1 of anlog output module No. 1 and set CH2 as mode 3 (current output: 0mA ~ +20mA).
2. Write H0 to CR#33 and allow OFFSET/GAIN tuning in CH1 and CH2.
3. When X0 goes from Off to On, write the OFFSET value K0
LSB
into CR#22 and the GAIN value K1,000
LSB
into
CR#28.
FROM/TO Application Example 4:
Adjust the D/A conversion curve of DVP-02DA. Set the OFFSET value of CH2 as 2mA (= K400
LSB
) and GAIN value
as 18mA (= K3,600
LSB
).
1. Write H10 to CR#1 of anlog output module No. 1 and set CH2 as mode 2 (current output: +4mA ~ +20mA).
2. Write H0 to CR#33 and allow OFFSET/GAIN tuning in CH1 and CH2.
3. When X0 goes from Off to On, write the OFFSET value K400
LSB
into CR#23 and the GAIN value K3,600
LSB
into
CR#29.
Summary of Contents for DVP-PLC
Page 1: ...PLC PLC...
Page 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Page 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Page 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Page 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...