7 Application Instructions API 50-99
D V P - P L C A P P L I C AT I O N M A N U A L
7-75
API Mnemonic
Operands
Function
78
D FROM P
Read CR Data in Special
Modules
Controllers
ES/EX/SS SA/SX/SC EH/SV
Bit Devices
Word Devices
Program Steps
Type
OP
X Y M S K H
KnX KnY KnM KnS T
C
D
E
F
m
1
*
*
*
m
2
*
*
*
D
*
*
*
*
*
*
*
*
n
*
*
*
FROM, FROMP: 9 steps
DFROM, DFROMP: 17 steps
PULSE 16-bit 32-bit
ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV
Operands:
m
1
: No. of special module
m
2
: CR# in special module to be read
D
: Device for storing read data
n
:
Number of data to be read at a time
Explanations:
1. Range
of
m
1
(16-bit and 32-bit): for ES/SA: 0 ~ 7, for EH/EH2 :0 ~ 255, for SV: 0 ~ 107.
2. Range
of
m
2
(16-bit and 32-bit): for ES/SA: 0 ~ 48, for EH: 0 ~ 254, for EH2/SV: 0 ~ 499.
3. Range
of
n
:
a) 16-bit: for ES/SA: 1 ~ (49 –
m
2
), for EH: 1 ~ (255 –
m
2
), for EH2/SV: 1 ~ (500 –
m
2
).
b) 32-bit: for ES/SA: 1 ~ (49 –
m
2
)/2, for EH: 1 ~ (255 –
m
2
)/2, for EH2/SV: 1 ~ (500 –
m
2
)/2.
4. ES series MPU does not support E, F index register modification.
5.
m
1
,
m
2
and
n
of EH series MPU do not support word device D.
6. Flag: M1083 (On when allowing interruptions during FROM/TO instruction).
7. This instruction is for reading the data in the CR in special modules.
8. The 16-bit instruction can designate
D
= K1 ~ K4; the 32-bit instruction can designate
D
= K1 ~ K8.
Program Example:
1. Read CR#29 of special module No.0 into D0 and CR#30 into D1. Only 2 groups of data is read at a time (n = 2).
2. When X0 = On, the instruction will be executed. When X0 = Off, the instruction will not be executed and the data
read will not be changed.
X0
FROM
K0
K29
D0
K2
Summary of Contents for DVP-PLC
Page 1: ...PLC PLC...
Page 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Page 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Page 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Page 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...