8 Application Instructions API 100-149
DVP-PLC Application Manual
8-22
API Mnemonic Operands
Function
109
SWRD P
Read Digital Switch
Controllers
ES/EX/SS SA/SX/SC EH/SV
Bit Devices
Word Devices
Program Steps
Type
OP
X Y M S K H
KnX
KnY KnM KnS T
C
D
E
F
D
*
*
*
*
*
*
*
*
SWRD, SWRDP: 3 steps
PULSE 16-bit 32-bit
ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV
Operands:
D
: Device for storing the read value
Explanations:
1. See the specifications of each model for their range of use.
2. Flags: M1104 ~ M1111 (status of digital switch)
3. This instruction stores the value read from digital switch function card into
D
.
4. The read value is stored in the low byte in D. Every switch has a corresponding bit.
5. When there is no digital function card inserted, the error message C400 (hex) will appear in grammar check.
Program Example:
1. There are l 8 DIP switches on the digital switch function card. After the switches are read by SWRD instruction,
the status of each switch will correspond to M0 ~ M7.
M1000
SWRD
K2M0
M0
Y0
M1
MOV
K2M0
D0
M2
CNT
C0
K10
M3
RST
C0
M4
TMR
T0
K100
2. The status of M0 ~ M7 can be executed by each contact instruction.
3. The execution of END instruction indicates that the process of input is completed. REF (I/O refresh) instruction
will be invalid.
4. When SWRD instruction uses the data in digital switch function card, it can read minimum 4 bits (K1Y*, K1M*
or K1S*).
Remarks:
When digital switch function card is inserted, the status of the 8 DIP switches will correspond to M1104 ~ M1111.
Summary of Contents for DVP-PLC
Page 1: ...PLC PLC...
Page 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Page 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Page 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Page 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...