7 Application Instructions API 50-99
D V P - P L C A P P L I C AT I O N M A N U A L
7 - 11
Counter
type
Program-interruption
high speed counter
Hardware high speed counter
1-phase 1 input
1-phase 1 input
1-phase 2 inputs
2-phase 2 inputs
Type
Input
C235 C236 C237 C238 C239 C240 C241 C242 C243 C244 C246 C247 C248 C249 C251 C252 C253 C254
X0
U/D
U/D
U
A
X1
U/D
D
B
X2
U/D
R
R
R
X3
U/D
S
S
S
X4
U/D
U/D
U
A
X5
U/D
D
B
X6 R
R
R
X7 S
S
S
X10
U/D
U
A
X11
D
B
X12 R
R
R
X13 S
S
S
X14
U/D
U A
X15
D B
X16
R
R R
X17
S
S S
U: Progressively increasing input
A: A phase input
S: Input started
B: Progressively decreasing input
B: B phase input
R: Input cleared
c) In EH/EH2/SV series MPU, there is no limitation on the times of using the hardware high speed counter
related instructions, DHSCS, DHSCR and DHSZ. However, when these instructions are enabled at the
same time, there will be some limitations. DHSCS instruction will occupy 1 group of settings, DHSCR 1
group of settings and DHSZ 2 groups of settings. There three instructions cannot occupy 8 groups of
settings in total; otherwise the system will ignore the instructions which are not the first scanned and
enabled.
d) System structure of the hardware high speed counters:
i) HHSC0 ~ 3 have reset signals and start signals from external inputs. Settings in M1272, M1274,
M1276 and M1278 are reset signals of HHSC0, HHSC1, HHSC2 and HHSC3. Settings in M1273,
M1275, M1277 and M1279 are start signals of HHSC0, HHSC1, HHSC2 and HHSC3.
ii) If the external control signal inputs of R and S are not in use, you can set M1264/M1266/M1268/M1270
and M1265/M1267/M1269/M1271 as True and disable the input signals. The corresponding external
inputs can be used again as general input points (see the figure below).
iii) When special M is used as a high speed counter, the inputs controlled by START and RESET will be
affected by the scan time.
Summary of Contents for DVP-PLC
Page 1: ...PLC PLC...
Page 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Page 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Page 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Page 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...