6 Application Instructions API 00-49
DVP-PLC Application Manual
6-67
2.
When X10 and X11 are On at the same time for less than 2 seconds, the present value of T10 will be reset to 0.
3.
When X3 goes from Off to On,
S896 ~ S1023 in SA/SX/SX are able to reset the annunciators in action.
S900 ~ S1023 in EH/EH2/SV are able to reset the annunciators in action.
4.
When X3 goes from Off to On again, the annuniator with secondary smaller No. will be reset.
X10
ANS
T10
K20
S910
X11
X3
ANRP
Remarks:
1. Flag:
a) M1048 (annunciator in action): When M1049 = On, any of the annunciators among S896 ~ S1023 in
SA/SX/SC or S900 ~ S1023 in EH/EH2/SV starts output, M1048 will be On.
b) M1049 (valid monitoring): When M1049 = On, D1049 will automatically display the annuciator of the
smallest number in action.
2.
Application of annunciators:
I/O point configuration:
X0: Forward switch
Y0: Forward
S910: Forward annunciator
X1: Backward switch
Y1: Backward
S920: Backward annunciator
X2: Front position switch
Y2: Annunciator indicator
X3: Back position switch
X4: Annunciatro reset button
Y0
ANS
T0
K100
S910
X2
X4
ANRP
M1000
M1049
Y1
ANS
T1
K200
S920
X3
X0
Y0
X2
M1048
Y2
Y0
X1
Y1
X3
Y1
1.
M1048 and D1049 are valid only when M1049 = On.
2.
When Y0 = On for more than 10 seconds and the device fails to reach the frong position X2, S910= On.
3.
When Y1 = On for more than 10 seconds and the device fails to reach the back position X3, S920= On.
Summary of Contents for DVP-PLC
Page 1: ...PLC PLC...
Page 28: ...1 Basic Principles of PLC Ladder Diagram DVP PLC Application Manual 1 24 MEMO...
Page 192: ...4 Step Ladder Instructions DVP PLC Application Manual 4 22 MEMO...
Page 472: ...8 Application Instructions API 100 149 DVP PLC Application Manual 8 70 MEMO...
Page 574: ...9 Application Instructions API 150 199 DVP PLC Application Manual 9 102 MEMO...