5 - 1 2
Modulon DPH Series
3
Take out the provided small copper bars and M8 screws from the UPS package, and
mount them on the four cooper bars that you just removed (see
)LJXUH
). For the
UPS’s package list, please refer to
3DFNDJH,QVSHFWLRQ
.
+
+
=
Different
Angle
Small Copper Bar
(Packed in the
UPS Package)
M8 Screws
(Packed in the
UPS Package)
Cooper Bar
(Removed from the
Wiring Terminals
According to
)
2
Tightening Torque = 150 ± 10 kgf-cm (130.2 ± 8.7 lb-in)
)LJXUH0RXQWWKH3URYLGHG6PDOO&RRSHU%DURQWKH5HPRYHG&RSSHU%DU
4
A.
For dual input and top wiring application, follow
)LJXUH
to install the removed four
copper bars (on which the small copper bars have been mounted according to
3
) in
the designated areas. Please secure the eight nuts tightly.
BYP
ASS
INPUT
AC
INPUT
L1
L2
L3
N
L1
L2
L3
N
Different
Angle
× 4
Install the Four
Copper Bars Here
Secure the Eight
Nuts Tightly
Install the Four
Copper Bars Here
Secure the Eight
Nuts Tightly
Cooper Bar
(on Which the Small
Copper Bar Has Been
Mounted According to )
3
Tightening Torque =
150 ± 10 kgf-cm (130.2 ± 8.7 lb-in)
)LJXUH,QVWDOOWKH)RXU&RSSHU%DUVDQG6HFXUHWKH(LJKW1XWVB
IRU'XDO,QSXW 7RS:LULQJ$SSOLFDWLRQ
B.
For dual input and bottom wiring application, follow
)LJXUH
to install the removed
four copper bars (on which the small copper bars have been mounted according to
3
) in the designated areas. Please secure the eight nuts tightly.
Summary of Contents for DPH-300K
Page 8: ......
Page 14: ......
Page 60: ......
Page 76: ......
Page 227: ...8 1 8 Optional Accessories 8 Optional Accessories ...
Page 230: ......
Page 231: ...9 1 9 Maintenance Maintenance ...
Page 233: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1 ...
Page 236: ......
Page 237: ...A2 1 Appendix 2 Warranty Warranty A2 A2 ...
Page 240: ... ...