6 - 2 9
6
UPS Operation
6.2.8 Energy Recycle Mode Start-up Procedures
WARNING:
Energy Recycle mode is only applicable to single input and single
unit application.
1
Ensure that the Manual Bypass Breaker (Q3), Output Breaker (Q4) and every external
battery cabinet’s breaker (Q5) are in the
OFF
position.
2
Switch
ON
the Input Breaker (Q1) and Bypass Breaker (Q2).
3
After you switch on the Input Breaker (Q1) and Bypass Breaker (Q2), each auxiliary
power card’s LED indicator will illuminate green and the following status will occur
simultaneously.
(1) The system and each power module will start initialization. After each power
PRGXOH¿QLVKHVLQLWLDOL]DWLRQHDFKSRZHUPRGXOH¶VIDQVZLOOVWDUWUXQQLQJ
(2) Each parallel communication card’s LED indicator will illuminate red first and
then each card will start initialization. After initialization, the master parallel
communication card’s LED indicator will illuminate green and the backup
communication card’s LED indicator will illuminate yellow.
For the locations of the parallel communication cards, auxiliary power cards, power
modules and their LED indicators, please refer to
)LJXUH
.
4
The
LCD
initial
screen
(see
)LJXUH
) will appear within 40 seconds after the Input
Breaker (Q1) and Bypass Breaker (Q2) are turned on.
)LJXUH/&',QLWLDO6FUHHQ
5
After 20 seconds of LCD initialization, the LCD will enter the
Main Screen
. For the
Main Screen
information, please refer to
0DLQ6FUHHQ
.
Summary of Contents for DPH-300K
Page 8: ......
Page 14: ......
Page 60: ......
Page 76: ......
Page 227: ...8 1 8 Optional Accessories 8 Optional Accessories ...
Page 230: ......
Page 231: ...9 1 9 Maintenance Maintenance ...
Page 233: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1 ...
Page 236: ......
Page 237: ...A2 1 Appendix 2 Warranty Warranty A2 A2 ...
Page 240: ... ...