7 - 4 6
Modulon DPH Series
On-Line
1
2
3
4
Security
Leakage
Fire
Smoke
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
LOG IN
Administrator
MEASUREMENT
EMS Setting
10:15
May 25,2018
EMS SETTING
INPUT
CONTACT
SENSOR
ID 0
EMS0
Title
ID
Status
Disable
Input
Contact
NO/NC
Title
Event Type
Normally Open
Normally Open
Normally Open
Normally Open
Warning
Warning
Warning
Warning
NOTE:
After connecting the optional EMS 1000 (EnviroProbe) to the UPS, you have to
manually set both
ID
and
Status
to enable the EMS function of the UPS. Settings
for the other items can be adjusted according to your needs; the default values are
VKRZQLQWKH¿JXUHVDERYH
Item
Sub Item
Description
SENSOR
ID
Set the ID # (ID 0/ ID 1/ …/ ID 15) according to the ID DIP
switch setting of the EMS 1000 (EnviroProbe) device.
NOTE:
If the ID # setting is wrong, the warning
message '
The EMS 1000 ID # Communication
Fail
' will appear.
Title
Set the title for each EMS 1000 (EnviroProbe) device.
Status
The status '
Enable
/
Disable'
determines whether or not
the LCD shows the EMS information of the EMS 1000
(EnviroProbe) device (ID #) on the screen.
Temperature
Set the temperature (°C) values for Alarm/ Warning/
Recovery.
Humidity
Set the humidity (%) values for Alarm/ Warning/ Recovery.
INPUT
CONTACT
Input Contact 1
1. Set the input contact as Normally Open (NO)/ Normally
Closed (NC).
2. Set the title for each input contact.
3. Set the event type as None/ Information/ Warning/ Alarm.
Input Contact 2
Input Contact 3
Input Contact 4
Summary of Contents for DPH-300K
Page 8: ......
Page 14: ......
Page 60: ......
Page 76: ......
Page 227: ...8 1 8 Optional Accessories 8 Optional Accessories ...
Page 230: ......
Page 231: ...9 1 9 Maintenance Maintenance ...
Page 233: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1 ...
Page 236: ......
Page 237: ...A2 1 Appendix 2 Warranty Warranty A2 A2 ...
Page 240: ... ...