The UPS runs in eight basic operation modes, which are On-Line mode, Battery mode, Bypass
mode, Manual Bypass mode, ECO mode, Frequency Conversion mode, Green mode and Energy
Recycle mode. Besides these eight operation modes, the UPS is also designed for common battery
application and hot standby redundancy. Please see the following sections for relevant information.
NOTE:
In this user manual, the meaning of Q1, Q2, Q3, Q4 and Q5 is shown as follows.
Code
Meaning
Q1
Input Breaker
Q2
Bypass Breaker
Q3
Manual Bypass Breaker
Q4
Output Breaker
Q5
External Battery Cabinet’s Breaker
3.1 Single
Input
3.1.1 On-Line Mode_ Single Input_ Single Unit
In On-Line mode, the main AC source supplies AC power via the Input Breaker (Q1) to the
UHFWL¿HUDQGWKHUHFWL¿HUFRQYHUWVWKH$&SRZHUWR'&SRZHUDQGVXSSOLHVWKH'&SRZHU
to the inverter. In the meantime, the rectifier provides charging power to the batteries.
After receiving the DC power, the inverter converts it into clean and stable AC power to the
connected critical loads via the Output Breaker (Q4). Please refer to
)LJXUH
. During On-
Line mode, the UPS’s tri-color LED illuminates green and the text '
On-Line
' appears in the
upper right corner of the screen.
MAIN
LOAD
Q1
Q2
Q4
Q3
Batteries
Rectifier
Inverter
Static Switch
Q5
)LJXUH2Q/LQH0RGH'LDJUDPB6LQJOH,QSXW6LQJOH8QLW
Summary of Contents for DPH-300K
Page 8: ......
Page 14: ......
Page 60: ......
Page 76: ......
Page 227: ...8 1 8 Optional Accessories 8 Optional Accessories ...
Page 230: ......
Page 231: ...9 1 9 Maintenance Maintenance ...
Page 233: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1 ...
Page 236: ......
Page 237: ...A2 1 Appendix 2 Warranty Warranty A2 A2 ...
Page 240: ... ...