6 - 1 4
Modulon DPH Series
2
Check if the bypass voltage and STS module are normal or not.
3
If normal, tap the ON/ OFF Button (
) and the following screen will pop up to
DVNLI\RXZDQWWRSRZHURႇWKH836¶VLQYHUWHU
On-Line
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
No
Yes
LOG IN
User
POWER OFF ?
Transfer to Bypass without Protection!
10:15
May 25,2018
)LJXUH3RZHURII5HPLQGHU6FUHHQ
4
If normal, please select '
YES
'. After that, the UPS will shut down the inverter and
transfer to run in Bypass mode.
5
(QVXUHWKDWWKH836UXQVLQ%\SDVVPRGH$IWHUFRQ¿UPDWLRQWXUQ
ON
the Manual
Bypass Breaker (Q3).
6
Switch
OFF
the Input Breaker (Q1), Bypass Breaker (Q2) and Output Breaker (Q4).
After that, the screen shows as follows.
Standby
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
0 %
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
LOG IN
User
2
WARNING
Power Flow
Summary
EMS
System Status
10:15
May 25,2018
)LJXUH2Q/LQH0RGHWR0DQXDO%\SDVV0RGH6FUHHQ