1 - 3
1
Important Safety Instructions
4. Each protective device could be a breaker or a fuse. For the protective device’s
rating current, please refer to the table below.
100kVA
150kVA
200kVA
250kVA
300kVA
200A
300A
400A
500A
630A
5. Each protective device should have the functions of over current protection, short
circuit protection, insulating protection and shunt trip feature. Please refer to the
table below for the UPS rated short-time withstand current (Icw).
100kVA
150kVA
200kVA
250kVA
300kVA
10kA
10kA
10kA
10kA
10kA
6. When selecting the protective devices, please take each power cable’s current
capacity and the system’s overload capacity (please refer to
Appendix 1: Technical
6SHFLILFDWLRQV
) into consideration. Besides, the short-circuit capacity of the
upstream protective devices must be equal to or larger than the capacity of the
UPS’s input protective devices.
7. Due to abnormalities in the UPS, the fault current may reach 20kA. At the time, the
UPS’s internal semi-conductor fuses will take 8 ~ 10 ms to open. Thus, the reaction
time of the upstream*
1
protective devices must be more than 10 ms so that the fuses
ZRXOGKDYHVXႈFLHQWWLPHWRLQWHUUXSWWKHIDXOWFXUUHQWDQGWKH836¶VE\SDVVZLOOEH
able to keep supplying power to the loads.
NOTE:
*
1
For dual input application, this refers to the bypass upstream.
8. If the UPS is supplied by a power source whose neutral is grounded, each protective
device must be a 3-pole type. If the UPS is supplied by a power source whose
neutral is not grounded, each protective device must be a 4-pole type.
9. The recommended electrical rating of the input, output and backfeed protective
devices are as follows. Application of the protective devices shall be in accordance
with local installation codes.
100kVA
150kVA
200kVA
250kVA
300kVA
690V
/
200A
690V
/
300A
690V
/
400A
690V
/
500A
690V
/
600A
1.3 Usage
Warnings
y
Before installation, wiring and working on the UPS’s internal circuits, please completely
FXWRႇDOOSRZHUVXSSO\LQJWRWKH836LQFOXGLQJWKHLQSXWSRZHUDQGEDWWHU\SRZHU
Summary of Contents for DPH-300K
Page 8: ......
Page 14: ......
Page 60: ......
Page 76: ......
Page 227: ...8 1 8 Optional Accessories 8 Optional Accessories ...
Page 230: ......
Page 231: ...9 1 9 Maintenance Maintenance ...
Page 233: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1 ...
Page 236: ......
Page 237: ...A2 1 Appendix 2 Warranty Warranty A2 A2 ...
Page 240: ... ...