3 - 1 2
Modulon DPH Series
3.1.12 Manual Bypass Mode_ Single Input_ Parallel Units
WARNING:
1. In Manual Bypass mode, make sure that all of the breakers (except each
Manual Bypass Breaker (Q3)) are in the
OFF
position before working on any of
the parallel UPSs’ internal circuits. This avoids electric shock.
$IWHUWKHSRZHULQVLGHHDFKRIWKHSDUDOOHO836VLVFRPSOHWHO\FXWRႇWKHUHLV
no high voltage inside all parallel UPSs and maintenance can be performed
safely. However, to avoid electric shock, please do not touch the following parts
on each parallel UPS: AC Input terminal block, Bypass Input terminal block,
UPS Output terminal block, Battery Input terminal block, grounding terminals
(see
)LJXUH
~
)LJXUH
for the location of these terminal blocks and
terminals) and any copper bars connected to the Manual Bypass Breaker (Q3),
as they may carry high voltage.
3. During Manual Bypass mode, each parallel UPS's input power is completely
FXWRႇDQGWKHFRQQHFWHGFULWLFDOORDGVDUHQRWSURWHFWHG
4. For parallel UPSs, if you want to turn off one of the parallel UPSs for
maintenance, please make sure the total connected critical loads will not
exceed the remaining parallel units’ total capacity.
In Manual Bypass mode (parallel), if one of the parallel UPSs needs maintenance, please
¿UVWFRQ¿UPWKDWWKHE\SDVV$&VRXUFHDQGHDFKSDUDOOHO836¶V676PRGXOHDUHQRUPDO
After confirmation, please follow the procedures below to manually switch each of the
parallel UPSs to Manual Bypass mode.
1
Tap each LCD’s ON/ OFF Button (
) and the '
POWER OFF?
' screen will pop up to
DVNLI\RXZDQWWRSRZHURႇWKH836¶VLQYHUWHU3OHDVHVHOHFW
'
YES
'.
2
Turn
ON
each UPS’s Manual Bypass Breaker (Q3).
3
Turn
OFF
each UPS’s Bypass Breaker (Q2).
4
Turn
OFF
each UPS’s Input Breaker (Q1) and Output Breaker (Q4).
5
Turn
OFF
each external battery cabinet’s breaker (Q5).
In Manual Bypass mode, all power inside the parallel UPSs is completely cut off and
maintenance personnel can perform maintenance safely. Power of the connected critical
loads will be supplied by manual bypass. During Manual Bypass mode (parallel), all parallel
836V¶WULFRORU/('VDQG/&'VDUHRႇ3OHDVHVHH
)LJXUH
for the path of electrical
power through the parallel UPSs in Manual Bypass mode.
Summary of Contents for DPH-300K
Page 8: ......
Page 14: ......
Page 60: ......
Page 76: ......
Page 227: ...8 1 8 Optional Accessories 8 Optional Accessories ...
Page 230: ......
Page 231: ...9 1 9 Maintenance Maintenance ...
Page 233: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1 ...
Page 236: ......
Page 237: ...A2 1 Appendix 2 Warranty Warranty A2 A2 ...
Page 240: ... ...