6 - 1 3
6
UPS Operation
6.2.4 Manual Bypass Mode Start-up Procedures
WARNING:
1. For parallel units, ensure that every operation procedure mentioned below is
synchronized to all parallel UPSs.
)RUSDUDOOHODSSOLFDWLRQLI\RXMXVWZDQWWRRSHUDWHDVSHFL¿F836EXWQRWDOO
parallel ones, please contact service personnel.
3. Please note that you can turn on the Manual Bypass Breaker (Q3) only when
the UPS needs maintenance. In Manual Bypass mode, power supply of the
connected critical loads comes from the manual bypass and the output is not
protected. Please ensure that the bypass AC source is normal.
4. In Manual Bypass mode, power supply of the critical loads comes from the
manual bypass; thus, maintenance personnel can perform maintenance
without interrupting the power supplying to the critical loads.
5. Ensure that all of the breakers (except the Manual Bypass Breaker (Q3)) are
in the
OFF
position, and use a voltmeter to check if there is any high voltage
LQVLGHWKH8362QO\DIWHU\RXKDYHFRQ¿UPHGWKDWWKHUHLVQRKLJKYROWDJHLQ
the UPS can service personnel perform UPS maintenance.
6. During the UPS maintenance process, do not touch the following parts: AC
Input terminal block, Bypass Input terminal block, UPS Output terminal block,
Battery Input terminal block, grounding terminals (see
)LJXUH
~
)LJXUH
for the location of these terminal blocks and terminals) and any copper bars
connected to the Manual Bypass Breaker (Q3), as they may carry high voltage.
y
From On-Line Mode to Manual Bypass Mode
1
In On-Line mode, the LCD’s main screen shows as follows and the tri-color LED
indicator illuminates green.
On-Line
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
30 %
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
LOG IN
User
Power Flow
Summary
EMS
System Status
10:15
May 25,2018
ON/ OFF
Button
)LJXUH2Q/LQH0RGH6FUHHQB8VHU/RJLQ 212))%XWWRQ/RFDWLRQ
Summary of Contents for DPH-300K
Page 8: ......
Page 14: ......
Page 60: ......
Page 76: ......
Page 227: ...8 1 8 Optional Accessories 8 Optional Accessories ...
Page 230: ......
Page 231: ...9 1 9 Maintenance Maintenance ...
Page 233: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1 ...
Page 236: ......
Page 237: ...A2 1 Appendix 2 Warranty Warranty A2 A2 ...
Page 240: ... ...