5 - 2 9
5
Installation and Wiring
5.6 External Battery Cabinet Connection Warnings
NOTE:
1. The information of the battery parameters in this chapter may not be applicable
to the lithium-ion batteries. For relevant information, please refer to the manual
of the lithium-ion batteries.
2. Whether you use the lead-acid batteries or the lithium-ion batteries, please
contact Delta service personnel for any battery/ battery cabinet’s setup and
FRQ¿JXUDWLRQV
y
You should connect the UPS with at least one external battery cabinet to ensure that the
connected critical loads are protected when a power failure occurs. You can connect up
to eight units of external battery cabinets to the UPS.
y
To ensure that the batteries are fully charged, please charge the batteries at least 8
KRXUVEHIRUH¿UVWXVHRIWKH8367KHFKDUJLQJSURFHGXUHVDUHDVIROORZV
1
Connect the UPS to the main AC source and the external battery cabinet(s).
Please see
,QVWDOODWLRQDQG:LULQJ
.
2
Follow
8362SHUDWLRQ
to turn on the UPS and the external battery cabinet(s).
After the UPS is turned on, the UPS will automatically charge the batteries.
WARNING:
You can connect the critical loads to the UPS only after the batteries are
IXOO\FKDUJHG7KLVJXDUDQWHHVWKDWWKH836FDQSURYLGHVXႈFLHQWEDFNXS
power to the critical loads connected when a power failure occurs.
y
Battery Parameters
No.
Item
Description
1
Charge Voltage
Float charge voltage: ±272Vdc (default)
Equalized charge voltage: ±280Vdc (default)
2
Charge Current
Default: ±5A (per power module)
Maximum: ±15A (per power module)
3
Low Battery Shutdown
Voltage
±200 ~ ±220Vdc (default: ±210Vdc)
4
The Number of Batteries
12V × 40 PCS (default)
Summary of Contents for DPH-300K
Page 8: ......
Page 14: ......
Page 60: ......
Page 76: ......
Page 227: ...8 1 8 Optional Accessories 8 Optional Accessories ...
Page 230: ......
Page 231: ...9 1 9 Maintenance Maintenance ...
Page 233: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1 ...
Page 236: ......
Page 237: ...A2 1 Appendix 2 Warranty Warranty A2 A2 ...
Page 240: ... ...