5 - 2 6
Modulon DPH Series
Parallel Cable
Parallel Ports
Parallel Ports
Parallel Ports
(Middle UPS(s))
(Last UPS)
Parallel Cable
Parallel Cable
(1 UPS)
st
)LJXUH3DUDOOHO3RUW&RQQHFWLRQB'DLV\&KDLQ0HWKRG
4
Follow the table below to select proper Protective Earth (PE) cables to ground the
parallel UPS units, external battery cabinet(s) and connected critical loads. The table
is in accordance with
IEC 60364-5-54
(
$UWLFOH
and
7DEOH
). The grounding
diagram below is for reference.
DPH Series 100-300kVA
Capacity
100kVA/
100kW
150kVA/
150kW
200kVA/
200kW
250kVA/
250kW
300kVA/
300kW
Suggested
PE Cable
Size
Input
16 mm
2
× 1 PC
(4 AWG
× 1 PC)
25 mm
2
× 1 PC
(2 AWG
× 1 PC)
25 mm
2
× 1 PC
(2 AWG
× 1 PC)
35 mm
2
× 1 PC
(1 AWG
× 1 PC)
50 mm
2
× 1 PC
(1/0 AWG
× 1 PC)
Bypass
16 mm
2
× 1 PC
(4 AWG
× 1 PC)
25 mm
2
× 1 PC
(2 AWG
× 1 PC)
25 mm
2
× 1 PC
(2 AWG
× 1 PC)
35 mm
2
× 1 PC
(1 AWG
× 1 PC)
50 mm
2
× 1 PC
(1/0 AWG
× 1 PC)
Suggested
PE Cable
Size
Output
16 mm
2
× 1 PC
(4 AWG
× 1 PC)
25 mm
2
× 1 PC
(2 AWG
× 1 PC)
35 mm
2
× 1 PC
(2 AWG
× 1 PC)
50 mm
2
× 1 PC
(1/0 AWG
× 1 PC)
67 mm
2
× 1 PC
(2/0 AWG
× 1 PC)
Battery
25 mm
2
× 1 PC
(2 AWG
× 1 PC)
25 mm
2
× 1 PC
(2 AWG
× 1 PC)
50 mm
2
× 1 PC
(1/0 AWG
× 1 PC)
50 mm
2
× 1 PC
(1/0 AWG
× 1 PC)
67 mm
2
× 1 PC
(2/0 AWG
× 1 PC)
Maximum Cable
Lug Width
48 mm
(1.89")
48 mm
(1.89")
48 mm
(1.89")
48 mm
(1.89")
48 mm
(1.89")
Screw Size/ Cable
Lug Inner Diameter
M10/ 14 mm (0.55")
Tightening Torque
M10 = 250 ± 10 kgf-cm (217 ± 8.7 lb-in)
Terminal Type*
1
TLAPH250-
2A12
TLAPH250-
2A12
TLAPH250-
2A12
TLAPH250-
2A12
TLAPH250-
2A12
Summary of Contents for DPH-300K
Page 8: ......
Page 14: ......
Page 60: ......
Page 76: ......
Page 227: ...8 1 8 Optional Accessories 8 Optional Accessories ...
Page 230: ......
Page 231: ...9 1 9 Maintenance Maintenance ...
Page 233: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1 ...
Page 236: ......
Page 237: ...A2 1 Appendix 2 Warranty Warranty A2 A2 ...
Page 240: ... ...