6 - 4 1
6
UPS Operation
Standy
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
No
Yes
LOG IN
User
POWER OFF ?
Transfer to Bypass without Protection!
10:15
May 25,2018
)LJXUH3RZHURII5HPLQGHU6FUHHQ
3
After selection of '
YES
', the UPS will shut down the inverter and terminate each power
module’s output. As there is no bypass output in Frequency Conversion mode, all
output will be terminated right after the inverter is shut down. Now, each power module
keeps charging the batteries, the tri-color LED indicator illuminates yellow and the
following screen appears (
)LJXUH
.
Standby
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
LOG IN
User
Load
0 %
Power Flow
Summary
EMS
System Status
10:15
May 25,2018
)LJXUH6WDQGE\0RGH6FUHHQ
4
Switch
OFF
the Output Breaker (Q4) and log in as an
Administrator
. For the
Admini-
strator
password, please contact service personnel. After login, ensure that you are in
the
Administrator
login status (see
)LJXUH
).
Summary of Contents for DPH-300K