6 - 4 3
6
UPS Operation
*UHHQ0RGH7XUQRႇ3URFHGXUHV
WARNING:
1. For parallel units, ensure that every operation procedure mentioned below is
synchronized to all parallel UPSs.
)RUSDUDOOHODSSOLFDWLRQLI\RXMXVWZDQWWRRSHUDWHDVSHFL¿F836EXWQRWDOO
parallel ones, please contact service personnel.
1
In Green mode, the LCD shows the following screen (
)LJXUH
and the tri-color
LED indicator illuminates green.
Green
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
30 %
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
LOG IN
User
Power Flow
Summary
EMS
System Status
10:15
May 25,2018
ON/ OFF
Button
)LJXUH*UHHQ0RGH6FUHHQ 212))%XWWRQ/RFDWLRQ
2
Tap the ON/ OFF Button (
) and the following screen will pop up to ask if you want
WRSRZHURႇWKH836¶VLQYHUWHU3OHDVHVHOHFW
YES
'.
Green
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
No
Yes
LOG IN
User
POWER OFF ?
Transfer to Bypass without Protection!
10:15
May 25,2018
)LJXUH3RZHURII5HPLQGHU6FUHHQ