6 - 3 5
6
UPS Operation
Battery
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
No
Yes
LOG IN
User
POWER OFF ?
Transfer to Bypass without Protection!
2
WARNING
10:15
May 25,2018
)LJXUH3RZHURII5HPLQGHU6FUHHQ
3
After selection of '
YES
', the UPS will shut down the inverter, terminate each power
module’s output and transfer to run in Standby mode. At this moment, the tri-color LED
indicator illuminates yellow and the following screen (
)LJXUH
appears.
Standby
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
0 %
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
LOG IN
User
2
WARNING
Power Flow
Summary
EMS
System Status
10:15
May 25,2018
)LJXUH6WDQGE\0RGH6FUHHQ
4
Switch
OFF
the Input Breaker (Q1), Bypass Breaker (Q2) and Output Breaker (Q4).
5
1RZHDFKSRZHUPRGXOHSHUIRUPV'&%86GLVFKDUJLQJDQGLWV/('LQGLFDWRUÀDVKHV
JUHHQ$IWHUGLVFKDUJLQJHDFKSRZHUPRGXOH¶V/('LQGLFDWRUZLOOEHRႇ
6
About 3 minutes later, the UPS will shut down, and the LCD and the tri-color LED
LQGLFDWRUZLOOEHRႇ
7
Switch
OFF
every external battery cabinet’s breaker (Q5).