6 - 3 2
Modulon DPH Series
Energy
Recycle
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
LOG IN
Administrator
2
WARNING
POWER FLOW
Maintenance
Bypass
Bypass
Mains
Load
0 %
0 %
0 mins
Power Flow
Summary
EMS
System Status
10:15
May 25,2018
)LJXUH(QHUJ\5HF\FOH0RGH6FUHHQ
7XUQRႇ3URFHGXUHV
2Q/LQH0RGH7XUQRႇ3URFHGXUHV
WARNING:
1. For parallel units, ensure that every operation procedure mentioned below is
synchronized to all parallel UPSs.
)RUSDUDOOHODSSOLFDWLRQLI\RXMXVWZDQWWRRSHUDWHDVSHFL¿F836EXWQRWDOO
parallel ones, please contact service personnel.
1
In On-Line mode, the LCD shows the following screen (
)LJXUH
and the tri-color
LED indicator illuminates green.
On-Line
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
30 %
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
LOG IN
User
Power Flow
Summary
EMS
System Status
10:15
May 25,2018
ON/ OFF
Button
)LJXUH2Q/LQH0RGH6FUHHQ 212))%XWWRQ/RFDWLRQ