1500 VA LCD 2U Rack UPS 
2200 VA LCD 2U Rack UPS 
3000 VA LCD 3U Rack UPS

 

 

 
 

Internal Battery 
Replacement Procedure 

Summary of Contents for 1500VA

Page 1: ...1500 VA LCD 2U Rack UPS 2200 VA LCD 2U Rack UPS 3000 VA LCD 3U Rack UPS Internal Battery Replacement Procedure...

Page 2: ......

Page 3: ...y grounded remove the utility source from the ground Contact with any part of a grounded battery can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed...

Page 4: ...ptible power supply from the rack cabinet 1 Press and hold the on off button until the long beep ceases approximately 3 seconds and then disconnect the uninterruptible power supply 2 Wait 60 seconds w...

Page 5: ...3 2 Loosen the thumbscrew on the metal battery cover 1 this may require the 5 flat head screwdriver slide the cover to the right 2 and open the cover 3...

Page 6: ...4 3 Disconnect the internal battery connector 1 and move connector on the battery out of the way and place the internal connector into the holder in the cover door...

Page 7: ...les might require two people to lift it Battery description Weight Handling requirement 1500 VA internal battery module 8 kg 18 lb One person 2200 VA internal battery module 16 3 kg 36 lb One person 3...

Page 8: ...6 7 With two hands four hands for a 3000 VA battery module slide the new battery module into the uninterruptible power supply 1...

Page 9: ...h the connector on the battery Note A small amount of arcing might occur when you connect the batteries This is normal and does not damage the unit or present any safety concern 9 Close the metal batt...

Page 10: ...8 10 To attach the uninterruptible power supply front bezel press the two side latches toward each other align the bezel with the uninterruptible power supply and snap it into place...

Page 11: ......

Page 12: ...This document was compiled and written by Christian Flatscher 2011 IBM Corp 2011 IBM UK Ltd...