Internal Battery Replacement Procedure 

 

WARNING 

This procedure may only be carried out by qualified personnel. 
 

CAUTION 

Lead-acid batteries can present a risk of electrical burn from high, short-

circuit current. Avoid battery contact with metal materials; remove watches, 
rings, or other metal objects, and use tools with insulated handles. To avoid 

possible explosion, do not burn. 
 

Exchange only with the IBM-approved part. Recycle or discard the battery as 

instructed by local regulations. In the United States, IBM has a process for 
the collection of this battery. For information, call 1-800-426-4333. Have the 

IBM part number for the battery unit available when you call. (C004) 

 
Servicing of batteries must be performed or supervised by personnel who are 

knowledgeable about batteries and the required precautions. Keep unauthorized 

personnel away from batteries. Batteries can present a risk of electrical shock or burn 
from high short-circuit current. 

 

Determine whether the battery is inadvertently grounded. If it is inadvertently 
grounded, remove the utility source from the ground. Contact with any part of a 

grounded battery can result in electrical shock. The likelihood of such shock can be 

reduced if such grounds are removed during installation and maintenance (applicable 
to equipment and remote battery supplies that do not have a grounded supply circuit). 

 
Replace batteries with the same number and type of batteries as originally installed in 

the uninterruptible power supply. Do not dispose of batteries in a fire. Batteries might 

explode when exposed to flame. 
 

Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and 

eyes and can be extremely toxic. 
 

The 2200 VA and 3000 VA uninterruptible power supply models might have an 

extended battery module option. 
 
If the message 

Service Battery

 

is displayed and the audible alarm is on continuously, 

you might have to replace the battery module. Contact your technical support 

representative to order new batteries. 
 

IMPORTANT 

Do not disconnect the batteries while the uninterruptible power supply is in Battery 
mode. Consider all warnings, cautions, and notes before you replace batteries. 

Disconnect the charging source before you connect or disconnect the battery 

terminals. 

Summary of Contents for 1500VA

Page 1: ...1500 VA LCD 2U Rack UPS 2200 VA LCD 2U Rack UPS 3000 VA LCD 3U Rack UPS Internal Battery Replacement Procedure...

Page 2: ......

Page 3: ...y grounded remove the utility source from the ground Contact with any part of a grounded battery can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed...

Page 4: ...ptible power supply from the rack cabinet 1 Press and hold the on off button until the long beep ceases approximately 3 seconds and then disconnect the uninterruptible power supply 2 Wait 60 seconds w...

Page 5: ...3 2 Loosen the thumbscrew on the metal battery cover 1 this may require the 5 flat head screwdriver slide the cover to the right 2 and open the cover 3...

Page 6: ...4 3 Disconnect the internal battery connector 1 and move connector on the battery out of the way and place the internal connector into the holder in the cover door...

Page 7: ...les might require two people to lift it Battery description Weight Handling requirement 1500 VA internal battery module 8 kg 18 lb One person 2200 VA internal battery module 16 3 kg 36 lb One person 3...

Page 8: ...6 7 With two hands four hands for a 3000 VA battery module slide the new battery module into the uninterruptible power supply 1...

Page 9: ...h the connector on the battery Note A small amount of arcing might occur when you connect the batteries This is normal and does not damage the unit or present any safety concern 9 Close the metal batt...

Page 10: ...8 10 To attach the uninterruptible power supply front bezel press the two side latches toward each other align the bezel with the uninterruptible power supply and snap it into place...

Page 11: ......

Page 12: ...This document was compiled and written by Christian Flatscher 2011 IBM Corp 2011 IBM UK Ltd...

Reviews: