Tools required 

1x #5 flat-head screwdriver 

 

Procedure 

To remove input power to change the battery, complete the following steps. 
 

Note:  Qualified personnel can replace internal batteries without shutting down the 

uninterruptible power supply and without having to remove the uninterruptible 
power supply from the rack cabinet. 

 

1.

 

Press and hold the on/off button until the long beep ceases (approximately 3 
seconds), and then disconnect the uninterruptible power supply. 

 

2.

 

Wait 60 seconds while the internal processor shuts down before you disconnect 

the battery. 

 
To replace the battery module, complete the following steps: 

 

1.

 

Remove the uninterruptible power supply front bezel. Press the two side latches 
toward each other to release the front bezel, and pull off the bezel. 

 

Summary of Contents for 1500VA

Page 1: ...1500 VA LCD 2U Rack UPS 2200 VA LCD 2U Rack UPS 3000 VA LCD 3U Rack UPS Internal Battery Replacement Procedure...

Page 2: ......

Page 3: ...y grounded remove the utility source from the ground Contact with any part of a grounded battery can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed...

Page 4: ...ptible power supply from the rack cabinet 1 Press and hold the on off button until the long beep ceases approximately 3 seconds and then disconnect the uninterruptible power supply 2 Wait 60 seconds w...

Page 5: ...3 2 Loosen the thumbscrew on the metal battery cover 1 this may require the 5 flat head screwdriver slide the cover to the right 2 and open the cover 3...

Page 6: ...4 3 Disconnect the internal battery connector 1 and move connector on the battery out of the way and place the internal connector into the holder in the cover door...

Page 7: ...les might require two people to lift it Battery description Weight Handling requirement 1500 VA internal battery module 8 kg 18 lb One person 2200 VA internal battery module 16 3 kg 36 lb One person 3...

Page 8: ...6 7 With two hands four hands for a 3000 VA battery module slide the new battery module into the uninterruptible power supply 1...

Page 9: ...h the connector on the battery Note A small amount of arcing might occur when you connect the batteries This is normal and does not damage the unit or present any safety concern 9 Close the metal batt...

Page 10: ...8 10 To attach the uninterruptible power supply front bezel press the two side latches toward each other align the bezel with the uninterruptible power supply and snap it into place...

Page 11: ......

Page 12: ...This document was compiled and written by Christian Flatscher 2011 IBM Corp 2011 IBM UK Ltd...