A H 5 0 0 H a r d w a r e a n d O p e r a t i o n M a n u a l
2 - 6 2
Functional specifications
Analog-to-digital
conversion
Centigrade (°C)
Fahrenheit (°F)
Input impedance
Rated input range
Pt100: -180°C~800°C
Ni100: -80°C~170°C
Pt1000: -180°C~800°C
Ni1000: -80°C~170°C
Pt100: -292°F~1,472°F
Ni100: -112°F~338°F
Pt1000: -292°F~1,472°F
Ni1000: -112°F~338°F
0~300
Ω
Average function
Range: 1~100
Self-diagnosis
Disconnection detection
AH08PTG-5A
Electrical specifications
Number of analog
inputs
8
Applicable sensor
Three-wire configuration: Pt100/Ni100/Pt1000/Ni1000 sensor, and 0~300
Ω
input impedance
Two-wire/Four-wire configuration: Pt100/Ni100/Pt1000/Ni1000 sensor, and
0~300
Ω
input impedance
Pt100: DIN 43760-1980 JIS C1604-1989; 100
Ω
3850 PPM/°C
Pt1000: DIN EN60751; 1 k
Ω
3850 PPM/°C
Ni100/Ni1000: DIN 43760
Supply voltage
24 VDC (20.4 VDC~28.8 VDC) (-15%~+20%)
Connector type
Removable terminal block
Overall accuracy
The error is ±1°C of a Pt100/Pt1000/Ni100/Ni1000 sensor’s temperature.
The error is ±0.1% of a resistance in the range of 0
Ω
to 300
Ω
.
Conversion time
Quick mode:
Four-wire/Two-wire configuration: 20 ms/channel
Three-wire configuration: 200 ms/channel
General mode: A conversion time will be gotten after the conversion time of
the two channels in a group is added up.
Four-wire/Two-wire configuration: 200 ms/channel
Three-wire configuration: 400 ms/channel
Isolation
An analog circuit is isolated from a digital circuit by a digital integrated circuit,
and the analog channels are isolated from one another by optocouplers.
Isolation between a digital circuit and a ground: 500 VDC
Isolation between an analog circuit and a ground: 500 VDC
Isolation between an analog circuit and a digital circuit: 500 VDC
Isolation between two group circuits: 500 VDC
Isolation between the 24 VDC and a ground: 500 VDC
Weight
255g
Functional specifications
Analog-to-digital
conversion
Centigrade (°C)
Fahrenheit (°F)
Input impedance
Rated input range
Pt100: -180°C~800°C
Ni100: -80°C~170°C
Pt1000: -180°C~800°C
Ni1000: -80°C~170°C
Pt100: -292°F~1,472°F
Ni100: -112°F~338°F
Pt1000: -292°F~1,472°F
Ni1000: -112°F~338°F
0~300
Ω
Average function
Range: 1~100
Self-diagnosis
Disconnection detection
Summary of Contents for AH500 series
Page 35: ...AH500 Hardware and Operation Manual 2 2 2 12 2 Profiles 2 117 2 12 3 Dimensions 2 118 ...
Page 153: ...AH500 Hardware and Operation Manual 2 120 MEMO ...
Page 167: ...AH500 Hardware and Operation Manual 3 14 MEMO ...
Page 343: ...AH500 Hardware and Operation Manual 6 38 MEMO ...
Page 361: ...AH500 Hardware and Operation Manual 7 18 MEMO ...
Page 403: ...Chapter 8 Hardware Configuration 8 42 MEMO ...
Page 412: ...Chapter 9 Network Configuration 9 9 ...
Page 445: ...AH500 Hardware and Operation Manual 9 42 MEMO ...
Page 552: ...Chapter 12 Troubleshooting 12 3 12 1 3 Troubleshooting Procedure ...
Page 649: ...AH500 Hardware and Operation Manual A 8 ...
Page 657: ...AH500 Hardware and Operation Manual A 16 MEMO ...
Page 658: ...B 1 Appendix B Device Addresses Table of Contents B 1 Device Addresses B 2 ...
Page 663: ...AH500 Hardware and Operation Manual C 4 MEMO ...
Page 681: ...AH500 Hardware and Operation Manual 3 14 MEMO ...