A H 5 0 0 H a r d w a r e a n d O p e r a t i o n M a n u a l
4 - 6 4
⑤
A relay or a solenoid valve is used as a DC load. A diode is connected in parallel to absorb the surge
voltage which occurs when the load is OFF.
⑥
An electromagnetic contactor is used as an AC load. A resistor and a capacitor are connected in
parallel to absorb the surge voltage which occurs when the load is OFF.
⑦
A bulb (incandescent lamp) is used as a DC load. A thermistor is connected in series to absorb the
surge current which occurs when the load is ON.
A bulb (neon lamp) is used as an AC load. A thermistor is connected in series to absorb the surge
current which occurs when the load is ON.
○
8
Mutually exclusive output: For example, Y0.4 controls the clockwise rotation of the motor, and Y0.5
controls the counterclockwise rotation of the motor. The interlock circuit which is formed, and the
program in the PLC ensure that there are protective measures if an abnormal condition occurs.
V DC power supply
Electromagnetic contactor
V DC power supply
Summary of Contents for AH500 series
Page 35: ...AH500 Hardware and Operation Manual 2 2 2 12 2 Profiles 2 117 2 12 3 Dimensions 2 118 ...
Page 153: ...AH500 Hardware and Operation Manual 2 120 MEMO ...
Page 167: ...AH500 Hardware and Operation Manual 3 14 MEMO ...
Page 343: ...AH500 Hardware and Operation Manual 6 38 MEMO ...
Page 361: ...AH500 Hardware and Operation Manual 7 18 MEMO ...
Page 403: ...Chapter 8 Hardware Configuration 8 42 MEMO ...
Page 412: ...Chapter 9 Network Configuration 9 9 ...
Page 445: ...AH500 Hardware and Operation Manual 9 42 MEMO ...
Page 552: ...Chapter 12 Troubleshooting 12 3 12 1 3 Troubleshooting Procedure ...
Page 649: ...AH500 Hardware and Operation Manual A 8 ...
Page 657: ...AH500 Hardware and Operation Manual A 16 MEMO ...
Page 658: ...B 1 Appendix B Device Addresses Table of Contents B 1 Device Addresses B 2 ...
Page 663: ...AH500 Hardware and Operation Manual C 4 MEMO ...
Page 681: ...AH500 Hardware and Operation Manual 3 14 MEMO ...