A H 5 0 0 H a r d w a r e a n d O p e r a t i o n M a n u a l
8 - 2 3
8.1.3.4 COM Port
If the CPU module is equipped with two communication ports, there are two setting areas for the two
communication ports, and the two communication ports are set individually.
You can select
RS232
,
RS485
, or
RS422
in the
Communication Type
drop-down list box. For AH560
Series PLC, only RS232 and RS485 are supported.
Users can set the communication protocol parameters. If the
RTU
option button is selected in the
Transfer
Mode
section, the
8 bit
option button in the
Data Length
section is automatically selected.
Users can set a station address. A device on a network can be identified by the station address of the
device. The station address of a device on a network can not be the same as the station address of
another device on the same network. The station address of a device must be in the range of 0 to 247.
If the communication port functions as a slave, and there are other slaves, the station address of the
communication port can not be 0, since station address 0 has the meaning of broadcasting to all slaves in
a communication protocol. If a master specifies in a data packet that data must be sent to station address
0, the data will be sent to all slaves. No matter what station address of these slaves are, these slaves will
receive the data packet.
If the sending of a command fails, the CPU module will retry the sending of the command. Users can set
the number of times the sending of a command is retired in this box. The number of times the sending of a
command is retired must be in the range of 0 to 20.
Users can set an interval of retrying the sending of a command. If the sending of a command fails, the
CPU module will retry the sending of the command every specific period of time. The interval of retrying
the sending of a command must be in the range of 100 milliseconds to 65535 milliseconds.
Summary of Contents for AH500 series
Page 35: ...AH500 Hardware and Operation Manual 2 2 2 12 2 Profiles 2 117 2 12 3 Dimensions 2 118 ...
Page 153: ...AH500 Hardware and Operation Manual 2 120 MEMO ...
Page 167: ...AH500 Hardware and Operation Manual 3 14 MEMO ...
Page 343: ...AH500 Hardware and Operation Manual 6 38 MEMO ...
Page 361: ...AH500 Hardware and Operation Manual 7 18 MEMO ...
Page 403: ...Chapter 8 Hardware Configuration 8 42 MEMO ...
Page 412: ...Chapter 9 Network Configuration 9 9 ...
Page 445: ...AH500 Hardware and Operation Manual 9 42 MEMO ...
Page 552: ...Chapter 12 Troubleshooting 12 3 12 1 3 Troubleshooting Procedure ...
Page 649: ...AH500 Hardware and Operation Manual A 8 ...
Page 657: ...AH500 Hardware and Operation Manual A 16 MEMO ...
Page 658: ...B 1 Appendix B Device Addresses Table of Contents B 1 Device Addresses B 2 ...
Page 663: ...AH500 Hardware and Operation Manual C 4 MEMO ...
Page 681: ...AH500 Hardware and Operation Manual 3 14 MEMO ...