24
Location 250: Power Up Condition
If a "1" is programmed in location 250 , the DL-300E will power-up disarmed if there is a total power shutdown and
battery failure. If a "2" is programmed in this location, it will power up armed. If this location contains a "0", the DL-300E
will maintain the condition it was in at power down. A watchdog circuit reset will cause the DL-300E to reset to the
selected condition. Factory default is "0" and the control will maintain the condition it was in at power down.
Location 251: Power Up Delay
The number programmed in location 251 represents the number of 10 second increments the DL-300E will delay before
accepting open or short inputs from any zone. Factory default is "0" and this feature is disabled. If a 6 is selected, the
delay will be 60 seconds. This delay period would also be initiated after a watchdog circuit reset condition or when exiting
from the program mode.
Location 252: Telephone Line Monitor
Location 252 determines the action the DL-300E will take when a phone line fault is detected. The options available are
listed in the table below. Program one or any combinations of these characteristics in location 252. Factory default is "0"
and the Phone line monitor is disabled. If
Enable silent (Value - 1),
is programmed then no code pad sounders or sirens
are activated but the auxiliary output option Category 15 and event 14 may be used. If
Enable sirens (Value
- 3) is
programmed, then the system siren will activate for the set siren time on a telephone line trouble condition.
Note:
A siren
can only be activated once per telephone line trouble condition, the telephone line trouble condition must restore be for
the siren can reactivate for a new telephone line trouble condition. If
Enable sirens (Value - 5)
is programmed, then the
system code pad sounder will activate until a valid code is entered, on a telephone line trouble condition. If
Enable sirens
(Value = 8)
is programmed, this siren will only activate when there is an Armed partition(s). In the event of a Phone line
fault the
"Ready LED"
on the led code pad will flash to indicate Phone line fault. The LCD code pad will display "PHONE
TROUBLE".
VALUE
TELEPHONE LINE MONITOR
0
DISABLED
1
ENABLES SILENT
3
ENABLES SIREN (timed)
5
ENABLES CODE PAD SOUNDER (latch)
7
ENABLES CODE PAD SOUNDER & SIREN
8
ACTIVATE SIRES ONLY WHEN SYSTEM ARMED
Location 253: Telephone Line Monitor
Delay
Location 253 contains the number of 10 second increments in the Telephone line monitor delay before phone line fault is
activated. The Telephone line monitor delay is used to overcome unnecessary telephone line faults caused by the momentary
removal of the DL-300E phone line socket. The Telephone line monitor delay can be programmed in 10 second increments
from 0 to 150 seconds ("0" = 0 seconds through "15" = 150 seconds). For example, programming a "2" in this location will
produce a Telephone line monitor delay of 20 seconds. Programming a "6" in this location will produce a Telephone line
monitor delay of 60 seconds. The phone line fault condition will not restore until the phone line is restored for the same period
of time as programmed in this location. Factory default is "1" for 10 seconds delay.
Location 254: Dynamic Battery Test
Time
The number programmed in location 254 determines when the control will perform a dynamic battery test. This time is
programmable in two hour increments from 12:00 AM to 10:00 PM. Possible values for this location are "0" thru "11 ". Factory
default is "3" (3 x 2 = 6) meaning the dynamic battery test will occur at 6:00 AM. Programming a "0" (0 x 2 = 0) in this
location would set the test time for 00:00 (midnight). Programming a "11 " (11 x 2 = 22) in this location would set the test
time for 22:00 (10:00 PM).