17
Location 208: Isolated Zone Code pad Sounder Alert
If a "1" is programmed in location 208, the code pad sounder will create a pulsed output if a valid code is utilized to arm the DL300E
when one or more zones are isolated. The code must be re-entered to silence the code pad buzzer. Factory default is "1" and code
pad sounder will sound when arming occurs with a zone isolated.
Location 209: AC Power Off Code pad Sounder Alert
If a "1" is programmed in location 209, the code pad buzzer will create a pulsed output if a valid code is used to arm the DL300E
with the AC power removed. The code must be re-entered to silence the code pad sounder. If a "0" is programmed in this location,
the control can be armed with the AC power removed with no code pad sounder output. Factory default is "1" and the code pad
sounder will sound if the control is armed with no AC power.
Location 210: Siren/Bell Test
Feature
Programming a "1" in location 210 will cause the siren/bell to sound each time the [1 ] and [7] keys are pressed simultaneously. The
siren/bell can be silenced with an arm/disarm code. The siren/bell test does not cause the communicator to transmit a message.
Factory default is "0" and this feature is not enabled.
Location 211: Partial Mode Security Feature
If a 1" is programmed in location 211, a valid user code must be entered to disarm the control from
the Partial Mode.
Factory
default is "0" and the
Partial
Mode
can be disarmed with the one digit code programmed in location 245.
Location 212: Ring back
Feature
Programming a "1" in location 212 will enable the Ring back feature of the DL-300E. When enabled, the control will create a two
second audible output (siren or bell) after the kiss-off tone from a closing signal has been received. Factory default is "0" 'and this
feature is not enabled.
Location 213: Multiple Partition First To Open, Last To Close Report
If a "1" is programmed in location 213 an opening report will be sent only after the first partition has been opened, and a closing
report will only be sent after all partitions have closed. All partitions must have enabled the opening and closing communicator
codes in the appropriate locations for this feature to work properly. Factory default is "0" and partitions will report opening and
closings individually according to the programming instructions entered for each partition.
Location 214: Resettable Auxiliary
Power
Programming a "1" in location 214 will cause the DL-300E (when in the disarmed state) to interrupt the smoke detector power each
time the [#] button is pressed. If this location contains a "0", pressing the [#] button will cause the smoke detector power to reset
only after zone(s) designated as Priority (FIRE) zone types are on steady for alarm or blinking for
Trouble.
Factory default is "1"
and this feature is enabled.
Location 215: Siren Output
Limit
If a "1" is programmed in location 215, the siren output will only activate once per zone during each arming cycle. Factory default is
"1" and this feature is enabled.