Location 155-170: Assigning Special Characteristics For Zones 1 -16

Locations 155 through 170 are used to assign zone characteristics for zones 1 through 16. Location 155 is for zone 1 and location 170 is
for zone 16. Each zone can have any or all of the following characteristics regardless of the zone type selected in locations 139-154
excluding Fire zones, which cannot have 

Isolate capability 

enabled. Factory default is "12 for each of these locations, meaning that

Zone Isolate Capability & Partial Mode is enabled, and the other characteristics are not enabled. To include other characteristics, add their
value, and program the sum in the appropriate location. See the table below for zone characteristics and their corresponding values.

PARTIAL MODE NOTES

* Zones containing a “4” will be monitored in the
Partial Mode.
* Zones not containing a “4” will be automatically
isolated in the Partial Mode.

VALUE

CHARACTERISTIC

1

Fast Loop Response

2

Group Isolate Zone

4

Partial Mode Zone

8

Zone Isolate Capability

Example 1

-

     To add Group Isolate Zone (Value=2) to Zone Isolate Capability (Value=8) for zone 10 (location 164),

           add the value of the two characteristics (2 + 8 = 10'), and program the sum of '10' in location 164.

Example 2

-

     To enable 

ALL 

characteristics for zone 10, add the value of all characteristics (1 + 2 + 4 + 8 ='15'),

           and program the sum of '15' in location 164 (zone 10 characteristics location).

Example 3

-

     To disable all characteristics and create a Non Isolatable Zone, program a'0' in the appropriate location

.

Location 171-186: Assigning Audible Characteristics For Zones 1 -16.

Locations 171-186 are used to assign the audible characteristics of each zone 1 through 16. Location 171 is for zone 1 and
location 186 is for zone 16. Each zone can be Silent (Value = ll), or have one, or a combination of the following audible
characteristics. To determine the appropriate data for these locations, refer to the chart below and add the sum of the
corresponding values to arrive at the correct data for these locations. For all zones except zone 2, factory default is "1". This
means that all 16 zones will create a yelp siren output when an alarm is created. To select the audible characteristics for any
zone, add the values of the audible characteristics from the table below, and program the sum in the appropriate locations
171186. If you wish for the zone to be 

Silent, 

program a "0" in the appropriate location. NOTE: If a Fire zone type is selected in

locations 139-154, standard fire zone characteristics will override any selection made for a zone in this section.

VALUE

AUDIBLE CHARACTERISTICS

1

Yelp Siren Audible

2

Steady Siren Audible

4

Code pad Sounder Audible

8

Chime Feature

0

Silent Zone

Summary of Contents for DL-300E

Page 1: ...PROGRAMMING THE AUXILIARY OUTPUTS P 18 13 PROGRAMMING FOR PARTITIONS P 22 14 REPORTING USER NUMBERS FOR VARIOUS FORMATS P 26 15 USERS 16 32 ARM DISARM CODE ENABLING P 29 16 LOCATIONS ACCESSIBLE THROUGH DOWNLOADING ONLY P 33 17 PROGRAMMIG WORKSHEETS P 34 44 18 APPENDIX 1 PROGRAMMING CONTACT I D FORMAT P 45 19 APPENDIX 2 PROGRAMMING SIA FORMAT P 46 20 APPENDIX 3 PROGRAMMING FORMAT OVERRIDES P 47 48 ...

Page 2: ...solated from the code pad if so enabled See page 14 for a description of all zone types Read the OPERATOR S MANUAL before you begin the installation for the best overall description of how the DL 300E functions After installation of the security system complete the information on page 1 of the operator s manual and explain the system operation to all security system owners operators QUANTITY PARTS...

Page 3: ...s programmed in Location 244 Assigning The Chime Code on page 23 of this manual Auto Isolate Enable When enabled in locations 205 the DL 300E can be armed with zones violated lacking a green Secure light on the code pad Under this condition all zones that are not secure at the end of the exit delay will become isolated All zones that become secured before the end of the exit delay will become acti...

Page 4: ...4 ...

Page 5: ...A approved transformer 32 33 Resettable 12VDC 250mA Aux power Memory reset and or Smoke detector power 34 36 Form C programmable on board relay output Tied to auxiliary output 3 37 Negative provided as a convenience for relay connection 38 39 Form A programmable on board relay output Tied to auxiliary output 4 40 41 Siren driver output to speaker s Min speaker rating 30 40 watt at 4 8 or 16 ohms S...

Page 6: ... method of code pad programming described below However with over 600 locations this method will be difficult except for the most experienced programmer When the FS4531 LED code pad is used for programming enter the factory default four digit Go To Program access code of 9 7 1 3 NOTE The DL300E must be disarmed to gain access to programming with this code After entry of this code the DL 300E will ...

Page 7: ...7 ...

Page 8: ...8 ...

Page 9: ...e can be used to enter the program mode To disable the Go To Program access code program a 15 in location 060 The factory default setting is 9 7 1 3 NOTE The first digit of this code should not match the Quick Arm digit NOTE If a 15 is programmed into location 60 to disable this code programming can only be accessed through the downloading software or with a plug in programmer Location 064 079 Use...

Page 10: ... take priority over phone 2 A 14 indicates the end of the phone number EXAMPLE Phone number 02 7244211 with touch tone dialing would be entered as 1 5 0 2 7 2 4 4 J 2 1 1 14 The 15 selects touch tone dialing and the 14 end the phone number Location 096 100 Programming The Account Code For Phone 1 Or Partition One The account code sent when phone 1 is dialed is programmed in locations 096 100 If th...

Page 11: ...eceiver to determine which format is compatible Select a format from the chart below If you require a format other than those listed review the override options described in locations 610 615 to build the appropriate format A 15 must be programmed in location 123 in addition to the entries into locations 610 615 in order to create a special format If this location contains a 0 the format programme...

Page 12: ...each number 2 The communicator attempts the number of dial attempts programmed into the number of dial attempts location to phone number 1 and if unsuccessful it will delay 5 minutes and attempt the same number of dial attempts programmed into number of dial attempts to phone number 2 4 Force the communicator to tie the account code to the phone number If this feature is not selected the account c...

Page 13: ... programmed in 10 second increments for 10 to 150 seconds 1 10 seconds through 15 150 seconds Note A 0 entry is treated as zero 0 seconds Programming a 6 in this location will produce an entry delay of 60 seconds Note a 0 entry is treated as zero 0 seconds Programming a 6 in this location will produce an entry delay of 60 seconds Factory default is 30 seconds Location 137 Programming The Secondary...

Page 14: ...ill initiate an entry delay It will be ignored during exit delay and when disarmed 5 HANDOVER Interior zone that follows the delay zones It is instant during non delay times Interior follower zones can be manually isolated before arming 6 INSTANT Produces an instant alarm if tripped when armed Ignored when disarmed 7 SECONDARY DELAY Like an EM Exit zone but has its own independent delay time 8 FIR...

Page 15: ...cteristics for zone 10 add the value of all characteristics 1 2 4 8 15 and program the sum of 15 in location 164 zone 10 characteristics location Example 3 To disable all characteristics and create a Non Isolatable Zone program a 0 in the appropriate location Location 171 186 Assigning Audible Characteristics For Zones 1 16 Locations 171 186 are used to assign the audible characteristics of each z...

Page 16: ...l not abort any reports NOTE The DL 300E will not abort unless a delay time is programmed in location 221 Location 204 Immediate Restore By Zone If a 1 is programmed in location 204 restore signals will follow the restore condition and report restores immediately after the condition has restored A non extended format will not send a Restore message until all zones and Trouble conditions have resto...

Page 17: ... and the Partial Mode can be disarmed with the one digit code programmed in location 245 Location 212 Ring back Feature Programming a 1 in location 212 will enable the Ring back feature of the DL 300E When enabled the control will create a two second audible output siren or bell after the kiss off tone from a closing signal has been received Factory default is 0 and this feature is not enabled Loc...

Page 18: ...tral station and the local siren or bell will not sound for these zones A zone trip will not be added to the number count until after the zone has tripped more than once If this location contains a 0 this feature is disabled A zone which has been isolated by this feature will be reported if Isolate Reporting is enabled in location 368 Location 220 This location must contain a 0 Location 221 Delay ...

Page 19: ...second increments from 2 to 28 seconds For example programming a 5 in the data 2 location will create a voltage trigger that would last for 10 seconds 2 x 5 10 seconds Programming a 0 will cause the output to follow the condition Programming a 15 will latch the trigger output Programming selections for this location are the numbers 0 thru 15 NOTE If you want to change the increments from seconds t...

Page 20: ...ROUBLE of individual zones 17 thru 32 9 0 15 ALARM of individual zones 1 thru 16 10 0 15 ALARM of individual zones 17 thru 32 11 0 15 Any FIRE ALARM 12 0 Any PANIC ALARM 1 Any BURGLARY ALARM 2 Any TROUBLE CONDITION 3 Any ISOLATE REPORT 4 Any EARLY TO OPEN 5 Any LATE TO CLOSE 6 AC FAILURE REPORT 7 DURESS 8 AUXILIARY 1 1 3 Double Keypress 9 AUXILIARY 2 4 6 Double Keypress 10 Code pad PANIC Double Ke...

Page 21: ...BLE LED illumination 15 ANY VALID CODE ENTRY 14 0 VAUD CODE ENTRIES 1 THRU 15 1 15 DOUBLE KEYPRESS 1 3 15 0 DOUBLE KEYPRESS 4 6 1 DOUBLE KEYPRESS 7 9 2 DOUBLE KEYPRESS 3 RESETTABLE AUXILUARY SMOKE DETECTOR POWER 4 DYNAMIC BATTERY TEST 5 LINE SEIZURE 6 OPEN ON ANY Zone 7 SHORT ON ANY Zone 8 OPEN OR SHORT ON ANY Zone 9 GROUND START 10 TIME OF OPENING 11 DOWNLOAD COMPLETE 12 FAILED T000MMUNICATE 13 P...

Page 22: ...is location will determine if the 4 auxiliary pins described in the above locations will create 2 to 28 second or 2 to 28 minute voltage trigger outputs If this location contains a 0 factory default 0 the output duration time is computed in seconds By adding the value that corresponds to each pin number in the table below and programming the sum in this location the second increments will convert ...

Page 23: ...ould be assigned to partition 2 You cannot assign zones out of sequence such as placing zones 1 3 5 7 9 in partition 1 and 2 4 6 8 in partition two Factory default is no partitions enabled and all zones are assigned to partition 1 the control without restriction Note When partitions are assigned in these locations you may need to program locations 64 79 124 131 132 213 217 224 228 232 236 246 and ...

Page 24: ...ue 5 is programmed then the system code pad sounder will activate until a valid code is entered on a telephone line trouble condition If Enable sirens Value 8 is programmed this siren will only activate when there is an Armed partition s In the event of a Phone line fault the Ready LED on the led code pad will flash to indicate Phone line fault The LCD code pad will display PHONE TROUBLE VALUE TEL...

Page 25: ...then the telephone number programmed in Data 4 for the selected communicator event is used to report that event If Dual or Split reporting is not enabled then program Data 4 to follow telephone number 1 for normal communicator event reporting I E Report via telephone number 1 and if unsuccessful try telephone number 2 If no Telephone is selected for a given communicator event that communicator eve...

Page 26: ...t event type is required The defaults are 3 0 7 5 with telephone number 1 and the event log enabled Location 284 287 Programming the Communicator Code for Zone 8 Locations 284 287 are used to control the communicator code for zone 8 Zone 8 is automatically enabled and when contact ID is selected the default report is event 130 Burglary with point 08 when in alarm Refer to appendix 1 if a different...

Page 27: ...he Communicator Code for Zone 16 Locations 316 319 are used to control the communicator code for zone 16 Zone 16 is automatically enabled and when contact I D is selected the default report is event 130 Burglary with point 16 when in alarm Refer to appendix 1 if a different event type is required The defaults are 3 1 6 5 with telephone number 1 and the event log enabled Location 320 322 Communicat...

Page 28: ...Pad for 1 minute if 30 or more key presses are made without producing a valid code The desired communicator code must be programmed into these locations to enable this feature When contact I D is selected program a 1 in Data 1 to report event 137 Code Pad Tamper No restore code is reported for this event If Data 1 is 0 the Code Pad Tamper is disabled The defaults are 1 0 0 5 with telephone number ...

Page 29: ...t if an arm disarm code is entered after an alarm on zones 1 through 32 has been reported excluding 24 hour zones After a cancel has been reported no zone restores will be transmitted on non 24 Hour zones When contact I D is selected program a one 1 in this location to enable this report the event code 406 will be reported followed by an opening event with the user code number used This feature ca...

Page 30: ...s locations per individual zone When contact I D is selected program a one 1 in this location to enable this report an event 570 Zone Isolate will be reported Default for Zone Isolate code is 0 enabled Location 369 Zone Isolate Code For Zones 9 Thru 16 4 2 Only These locations should remain at factory default when Contact I D is selected Location 370 Zone Isolate Code For Zones 17 Thru 24 4 2 Only...

Page 31: ...face Telephone control interface and System event interface Factory default is 0 no devices enabled These locations must remain at factory default when no expansion systems are used Location 378 Communicator Code for Expansion Trouble Location 378 is used to program reporting Trouble communicator code for expander devices 1 thru 7 when Contact I D is selected The Expander Trouble communicator code...

Page 32: ...sum of 15 in location 399 zone 10 characteristics location Example 3 To disable all characteristics and create a Non Isolatable Zone program a 0 In the appropriate location Location 412 427 Assigning Audible Characteristics For Zones 17 32 Locations 412 427 are used to assign the audible characteristics zones 17 through 32 Location 412 is for zone 17 and location 427 is for zone 32 Each zone can b...

Page 33: ...Code for Zone 18 Locations 448 451 are used to control the communicator code for zone 18 Zone 18 is automatically enabled and when contact ID is selected the default report is event 130 Burglary with point 18 when in alarm Refer to appendix 1 if a different event type is required The defaults are 3 1 8 5 with telephone number 1 and the event log enabled Location 452 455 Programming the Communicato...

Page 34: ...ol the communicator code for zone 26 Zone 26 is automatically enabled and when contact I D is selected the default report is event 130 Burglary with point 26 when in alarm Refer to appendix 1 if a different event type is required The defaults are 3 2 6 5 with telephone number 1 and the event log enabled Location 484 487 Programming the Communicator Code for Zone 27 Locations 484 487 are used to co...

Page 35: ...ED SYSTEMS If partitions are utilized codes may be assigned to a specific partition by using locations 572 586 This is done by disabling each individual code code 16 location 572 thru code 30 location 586 for each of the four partitions that code should not have access to Codes are selected by adding the binary equivalents for each partition together and programming that number in the proper locat...

Page 36: ...ate closing report a 4 digit 24 hour closing time must be entered in locations 604 607 For example to enter a closing time of 6 30 p m 1830 program a 1 in location 604 a 8 in location 605 a 3 in location 606 and a 0 in location 607 Factory default is a 2 0 0 0 which sets a closing time of 8 00PM NOTE A communicator code must be entered in location s 588 590 if this feature is selected Location 608...

Page 37: ...main a zero 0 If the selected interval is every 75 days you would program a 7 in location 620 and a 5 in location 621 Locations 340 342 must be programmed to enable autotest reporting Location 622 Automatic Download Callback Enable Programming a 1 in location 622 will cause the control panel to automatically call the download computer callback number at every autotest interval This feature will no...

Page 38: ...ns digit The time is entered in 24 hour time If the current time is 5 25 PM the 24 hour time is 17 25 so this location should contain a 1 which is the current hour tens digit If the current time is 9 36 AM the 24 hour time is 09 36 so this location should contain a 0 Location 633 Programming The Current Hour Ones Digit Location 633 contains the current hour ones digit The time is entered in 24 hou...

Page 39: ...ures below can be obtained by programming the appropriate data in this location The correct data can be obtained by ADDING the values of the corresponding characteristics from the table below possible values are 0 to 7 VALUE CHARACTERISTIC 1 Panel will automatically callback for download session 2 Site initiated download call by entering 9 8 at code pad and or automatic callback if a 1 is programm...

Page 40: ...ABLED 052 055 8 USER 14 ARM DISARM CODE 15 DISABLED 056 059 8 USER 15 ARM DISARM CODE 15 DISABLED 060 063 8 GO TO PROGRAM ACCESS CODE 9 7 1 3 ENABLING ARM DISARM CODES 1 16 BY PARTITION OPTIONAL LOCATION PAGE DESCRIPTION DATA DEFAULT 64 9 PARTITION S FOR USER 1 ARM DISARM CODE 15 ALL 65 9 PARTITION S FOR USER 2 ARM DISARM CODE CE ALL 66 9 PARTITION S FOR USER 3 ARM DISARM CODE 15 ALL 67 9 PARTITIO...

Page 41: ...ELECTING PHONE SEQUENCE LOCATION PAGE DESCRIPTION FORMAT DEFAULT 132 11 PHONE SEQUENCE CONTROLLER 0 DISABLED DATA FORMAT DESCRIPTION 0 LOCAL ONLY COMMUNICATOR IS DISABLED 1 ADEMCO CONTACT ID DTMF FORMAT 2 ADEMCO 4 2 EXPRESS DTMF FORMAT 3 FBI SUPERFAST 2300HZ 4 ADEMCO HIGHSPEED DTMF FORMAT 5 RADIONICS EXTENDED SLOW 1800HZ TRANSMITTAL 2300HZ 20 PPS HEX EXTENDED DOUBLE ROUND 6 CADDX MODEM PROPRIETARY...

Page 42: ...ONETYPE 9 Keyswitch s INSTANT 150 13 ZONE 12 ZONETYPE 6 INSTANT 151 13 ZONE 13 ZONE TYPE 6 INSTANT 152 13 ZONE 14 ZONE TYPE 6 INSTANT 153 13 ZONE 15 ZONE TYPE V INSTANT 154 13 ZONE 16 ZONE TYPE 6 INSTANT 155 14 ZONE 1 SPECIAL CHARACTERISTICS 12 156 14 ZONE SPECIAL CHARACTERISTICS LOCATIONS 155 170 12 157 14 ZONE 3 SPECIAL CHARACTERISTICS VALUE CHARACTERISTIC 12 158 14 ZONE 4 SPECIAL CHARACTERISTIC...

Page 43: ...2 REPORTING CHARACTERISTICS 11 189 15 ZONE 3 REPORTING CHARACTERISTICS 11 190 15 ZONE 4 REPORTING CHARACTERISTICS 11 191 15 ZONE 5 REPORTING CHARACTERISTICS 11 192 15 ZONE 6 REPORTING CHARACTERISTICS 11 193 15 ZONE 7 REPORTING CHARACTERISTICS 11 194 15 ZONE 8 REPORTING CHARACTERISTICS LOCATIONS 187 202 11 195 15 ZONE 9 REPORTING CHARACTERISTICS VALUE REPORTING CHARACTERISTICS 11 196 15 ZONE 10 REP...

Page 44: ...N PAGE DESCRIPTION DATA 1 DATA 2 DATA 3 DATA 4 DEFAULT 224 227 18 PIN 1 0 0 13 10 228 231 18 PIN 2 0 0 13 11 232 235 18 PIN 3 0 15 13 2 236 239 18 PIN 4 0 0 13 2 COMMUNICATOR CODES CONTINUED LOCATION PAGE DESCRIPTION DATA DEFAULT 240 20 INVERTING THE AUXILIARY OUTPUTS 0 241 21 TIMIMG INCREMENTS FOR AUXILIARY OUTPUTS 0 242 21 ANSWERING MACHINE DEFEAT OPTIONS 1 TO 3 RINGS 0 DISABLED 243 21 NUMBER OF...

Page 45: ... COMMUNICATOR CODE 3 1 6 5 COMMUNICATOR CODES CONTINUED LOCATION PAGE DESCRIPTION DATA 1 DATA 2 DATA 3 DATA 4 DEFAU LT 320 323 24 DURESS COMMUNICATOR CODE 0 0 0 5 324 327 24 CODE PAD 1 3 AUXILIARY 1 REPORT CODE 0 0 0 5 328 331 25 CODE PAD 4 6 AUXILIARY 2 REPORT CODE 0 0 0 5 332 335 25 CODE PAD PANIC REPORT CODE 2 0 0 5 336 339 25 CODE PAD TAMPER REPORT CODE 0 0 0 5 340 343 25 AUTO TEST REPORT CODE...

Page 46: ...28 ZONE ISOLATE CODE FOR ZONES 25 32 0 DISABLED 376 28 AC POWER LOW BATTERY RESTORE CODE 0 DISABLED 377 28 NUMBER OF EXPANSION MODULES 0 DISABLED 378 28 EXPANSION MODULE TROUBLE COMMUNICATOR CODE 0 DISABLED 379 28 EXPANSION MODULE TROUBLE REPORT TO WHICH PHONE NUMBER 0 PHONE 1 380 28 ZONE 17 ZONE TYPE LOCATIONS 380 395 6 INSTANT 381 28 ZONE 18 ZONE TYPE DATA ZONE TYPES 6 INSTANT 382 28 ZONE 19 ZON...

Page 47: ...ERISTICS VALUE AUDIBLE CHARACTERISTIC 1 414 28 ZONE 19 AUDIBLE CHARACTERISTICS 1 Yelp Siren Audible 1 415 28 ZONE 20 AUDIBLE CHARACTERISTICS 2 Steady Siren Audible 1 416 28 ZONE 21 AUDIBLE CHARACTERISTICS 4 Keypad Sounder Audible 1 417 28 ZONE 22 AUDIBLE CHARACTERISTICS 8 Chime Feature 1 418 28 ZONE 23 AUDIBLE CHARACTERISTICS 0 Silent Zone 1 419 28 ZONE 24 AUDIBLE CHARACTERISTICS 1 420 28 ZONE 25 ...

Page 48: ...MMUNICATOR CODE 3 2 1 5 464 467 28 ZONE 22 COMMUNICATOR CODE 3 2 2 5 468 471 28 ZONE 23 COMMUNICATOR CODE 3 2 2 5 472 475 28 ZONE 24 COMMUNICATOR CODE 3 2 3 5 476 479 28 ZONE 25 COMMUNICATOR CODE 3 2 5 5 480 483 28 ZONE 26 COMMUNICATOR CODE 3 2 6 5 484 487 28 ZONE 27 COMMUNICATOR CODE 3 2 7 5 488 491 28 ZONE 28 COMMUNICATOR CODE 3 2 8 5 492 495 28 ZONE 29 COMMUNICATOR CODE 3 2 9 5 496 499 28 ZONE ...

Page 49: ...IONS FOR USER 22 ARM DISARM CODE 8 Partition 4 15 ALL 579 29 PARTITIONS FOR USER 23 ARM DISARM CODE 15 ALL 580 29 PARTITIONS FOR USER 24 ARM DISARM CODE NON PARTITIONED SYSTEMS 15 ALL 581 29 PARTITIONS FOR USER 25 ARM DISARM CODE VALUE CHARACTERISTIC 15 ALL 582 29 PARTITIONS FOR USER 26 ARM DISARM CODE 1 Standard Arm Disarm Code 15 ALL 583 29 PARTITIONS FOR USER 27 ARM DISARM CODE 2 Arm Only After...

Page 50: ...27 31 CURRENT MONTH JANUARY 1 THROUGH DECEMBER 12 UNDEFINED 628 32 CURRENT DAY OF THE MONTH TENS DIGIT 21ST 2 UNDEFINED 629 32 CURRENT DAY OF THE MONTH ONES DIGIT 21ST 1 UNDEFINED 630 32 CURRENT YEAR TENS DIGIT UNDEFINED 631 32 CURRENT YEAR ONES DIGIT UNDEFINED 632 32 CURRENT HOUR TENS DIGIT UNDEFINED 633 32 CURRENT HOUR ONES DIGIT UNDEFINED 634 32 CURRENT MINUTE TENS DIGIT UNDEFINED 635 32 CURREN...

Page 51: ...g 24 Hour 10 121 Duress 11 100 Medical Alarm 12 123 Audible Panic If the following numbers are programmed for the contact ID event code the event code will be made up of 3 alternate programming locations according to the following PROGRAMMED 100 s DIGIT PROGRAMMING LOCATIONS 13 365 366 367 14 369 370 371 15 373 374 375 The following event codes are sent automatically but must be enabled by program...

Page 52: ...owing event codes are fixed but must be enabled by programming a 1 in the corresponding location REPORTING EVENT SIA CODE LOCATION TAMPER TA 336 AUTOTEST RP 340 CHECKSUM ERROR YF 344 OPENING OP 348 CLOSING CL 350 CANCEL OC 354 AC LOSS AT 356 LOW BATTERY YT 360 RESTORE CODE R 364 BYPASS CODE B 368 BYPASS RESTORE U 368 364 TROUBLE CODE T 372 TROUBLE RESTORE R 372 364 AC RESTORE AR 376 BATTERY RESTOR...

Page 53: ...appropriate location If the value is not added for locations 612 and 613 the converse mode will be enabled for those locations If the value of 1 is not added to location 612 the transmitted frequency will be 1900 Hz If the value of 2 is not added to location 613 the communicator will not transmit hex digits If neither of values 4 or 8 are added of location 613 the communicator will send messages a...

Page 54: ... AND WORKMANSHIP FOR TWENTY FOUR 24 MONTHS FROM DATE OF PURCHASE IF ANY DEFECT APPEARS DU AINGTHE WARRANTY PERIOD RETURN IT TO DAS POSTAGE PREPAID THE UNIT WILL BE REPAIRED AND RETURNED DAS ASSUMES NO LIABILITY FOR CONSEQUENTIAL OR INDIRECT DAMAGE AND ACCEPTS NO RESPONSIBILITY FOR REPAIRING DAMAGE TO THE PRODUCT CAUSED BY MISUSE CARELESS HANDLING OR WHERE REPAIRS HAVE BEEN MADE BY OTHERS NO OTHER ...

Page 55: ...55 ...

Page 56: ...56 ...

Page 57: ...57 ...

Reviews: